A factory, waterworks or power station is run from one room where every pressure, temperature, level and flow arrives on a dial, is drawn on a moving chart, and rings an alarm when it goes wrong. How measurements are sent along a pipe or a pair of wires, how to build pressure and temperature transmitters, clockwork and self-balancing chart recorders and simple data loggers, and how to lay out a control panel with alarms that people trust.

Difficulty
●●●●●
Time
A week for a clockwork drum recorder; a month for a self-balancing recorder; a season to equip a control room
Steps from zero
55 prerequisites →

You need first

Measuring ElectricityWater and Gas MetersThermostats and Automatic Control

This unlocks

Process Controllers and Control ValvesTelemetry and Remote Control

Raw materials

hardwoodslate
The full path from nothing — 55 steps before this one
  1. Fire
  2. Cordage and Rope
  3. Stone Tools
  4. Finding and Preparing Clay
  5. Finding and Identifying Ores
  6. Measurement from Scratch
  7. Writing and Numbers
  8. Hunting and Trapping
  9. Basic Woodworking
  10. Charcoal
  11. Pottery
  12. The Kiln
  13. Arithmetic and Fractions
  14. Hides and Leather
  15. Tiles and Clay Pipes
  16. Salt
  17. Lime
  18. Bricks
  19. Surveying and Levelling
  20. Fermentation
  21. Lye and Potash
  22. The Wheel and Axle
  23. Glass
  24. Firebrick and Refractories
  25. Bellows
  26. Distillation
  27. The Lathe
  28. Gears
  29. Copper Smelting
  30. Iron (the Bloomery)
  31. Lead
  32. Laboratory Glassware
  33. Pumps
  34. The Waterwheel
  35. Blacksmithing
  36. The Blast Furnace and Cast Iron
  37. Pipes, Plumbing and Aqueducts
  38. The Battery
  39. The Thermometer
  40. Steel
  41. The Steam Engine
  42. Bellows to Air Compressors
  43. Copper Wire
  44. Electrolysis
  45. Hydrogen, Oxygen and Gases
  46. Machine Tools
  47. Petroleum and Refining
  48. The Electromagnet
  49. Ammonia
  50. Measuring Electricity
  51. Thermostats and Automatic Control
  52. Ice and Refrigeration
  53. Liquid Air, Nitrogen and the Noble Gases
  54. Natural Gas and Helium
  55. Water and Gas Meters
  56. Instruments, Chart Recorders and Control Rooms

Do them roughly in this order. See it on the tech tree →

Why it matters

A small works can be run by walking round it: look at the boiler gauge, tap the tank, feel the bearing. A large one cannot. A waterworks may have reservoirs kilometres apart, a power station a thousand readings, a chemical plant reactions that run away in minutes. Instruments that send their readings to one room, record them on paper, and raise an alarm let a few people run it safely, day and night.

The record matters as much as the reading. A chart proves that the water was disinfected every hour of the week (Water Treatment for a Town), shows the slow rise in a bearing temperature that warns of failure, and tells the engineer after an accident what happened and in what order. A works with good records gets better every year (The Scientific Method, Statistics and Probability).

How it works

A measurement starts as a movement. A Bourdon tube straightens with pressure (Pressure and Vacuum Gauges); a bimetal strip bends with heat and a capsule swells (Thermostats and Automatic Control); a float rises with level; a meter counts flow (Water and Gas Meters). Read nearby, the movement turns a pointer. To read it far away, it has to be turned into something that travels.

Three ways to send a reading.

Signal Range How far Notes
Filled capillary the measured pressure or a sealed liquid up to about 30–50 m No power; slow; a capillary can be crushed
Pneumatic 0.2 to 1.0 bar (3–15 psi) air pressure up to about 300 m Safe near flammable gas; needs clean dry air
Electric current 4 to 20 mA kilometres The modern standard

Why a current, not a voltage. In a series loop the same current flows all round, whatever the resistance of the wires. A voltage would sag along a long cable and read low. Why 4 mA, not 0. The "live zero": 4 mA means 0 % of the range, 20 mA means 100 %. A broken wire or dead transmitter gives 0 mA, which is obviously a fault, not a low reading. And 4 mA is enough current to power the transmitter itself over the same two wires.

Pneumatic signals do the same: 0.2 bar is zero, 1.0 bar is full scale, and no air means a fault.

pressure Transmitter set to 0–10 bar Power supply 24 V Indicator at the pump house Recorder in the control room Alarm unit trips at a set current the same current flows all round the loop 4 mA8 mA12 mA16 mA20 mA 0 bar2.557.510 bar 0 mA fault
Fig. 1 A 4–20 mA current loop. The transmitter, a power supply, an indicator, a recorder and an alarm unit are all connected in one series loop by two wires. The same current flows through all of them, so each reads the same value however long the wires are.

Converting the reading. For a transmitter set to 0–10 bar, the current is 4 mA plus 16 mA times the fraction of full scale:

  • 0 bar → 4 mA; 2.5 bar → 8 mA; 5 bar → 12 mA; 10 bar → 20 mA.
  • Reading back: pressure = (current − 4) ÷ 16 × 10 bar.

The pressure transmitter

Simplest: the slide-wire transmitter

  1. Sensing element. A Bourdon tube or a corrugated diaphragm. A diaphragm of phosphor bronze or brass 0.1–0.2 mm thick and 50–80 mm across, pressed with 3–5 concentric ripples, clamped between two flanges (Sheet Metal and Rolling, Zinc and Brass), gives a good low-pressure element. A spring behind it sets the range.
  2. Slide-wire. A length of resistance wire (Resistors, Capacitors and Coils) wound evenly on an insulating former, with a light contact (the wiper) moved by the element through a lever. With a steady voltage across the wire, the wiper voltage is a fraction of it proportional to pressure.
  3. Reading. Three wires carry this to a voltmeter or, better, a ratio meter or bridge in the control room, so that a change in supply voltage cancels out. Good to 1–2 %.

Force-balance pneumatic transmitter

A fine nozzle blows air against a flat flapper. When the flapper nearly covers the nozzle, pressure builds up behind it. Pressure on a diaphragm pushes the flapper one way; a feedback bellows, fed with the output air, pushes it back. The output settles at whatever pressure balances the force. Nothing moves more than a few hundredths of a millimetre, so there is no wear and little error. Supply clean, dry air at about 1.4 bar (Bellows to Air Compressors), filtered and with water drained from a trap.

Electronic strain-gauge transmitter

Bond four strain gauges to a stiff steel diaphragm in a bridge. Pressure bends the diaphragm a few micrometres and unbalances the bridge by a few millivolts. An amplifier (Amplifiers and Oscillators) turns this into a current regulated at 4–20 mA, powered from the loop itself. Set zero (4 mA with no pressure) and span (20 mA at full pressure) with two small trimming resistors, against a dead-weight tester (Pressure and Vacuum Gauges).

Level and flow from pressure

  • Level: the pressure at the bottom of a tank is the depth times the liquid's weight: 1 m of water = 0.098 bar (9.8 kPa). A transmitter at the bottom of a reservoir reads its level directly. For a 5 m reservoir, range it 0–0.5 bar.
  • Flow: the pressure difference across an orifice plate or venturi (Water and Gas Meters) rises as the square of the flow. A differential transmitter measures it; the square root must be taken (by a cam, a scale or a calculation) to read flow. At 10 % of full flow the difference is only 1 % of full scale, so orifice flowmeters are poor at low flows.

Tip Fit a valve and a tee in every pipe to an instrument (the impulse line), so the transmitter can be shut off, vented and checked against a test gauge without stopping the plant. On steam, put a coiled pigtail of water between the pipe and the instrument (Pressure and Vacuum Gauges).

The temperature transmitter

The two electrical sensors used in works are:

  • The thermocouple (Thermocouples and Thermoelectricity): two different wires welded at the hot end. Iron with constantan gives about 52 µV per °C; nickel-chromium with nickel-aluminium about 41 µV per °C, and lasts to about 1,100 °C. It reads the difference between the hot end and the cold junction where it joins copper wires, so the cold junction must be kept at a known temperature (in melting ice in the laboratory) or its temperature measured and added. Use extension wires of the same metals all the way to the cold junction.
  • The resistance thermometer (Photocells and Sensors): a coil of fine platinum or nickel wire. Platinum of 100 Ω at 0 °C rises about 0.385 Ω per °C. More exact than a thermocouple below about 500 °C. Use three wires to the bridge so the lead resistance cancels.

A temperature transmitter is a small box at the sensor holding a bridge or cold-junction circuit and an amplifier, with a 4–20 mA output. Without electronics, a millivolt galvanometer wired straight to a thermocouple (Thermocouples and Thermoelectricity) reads furnace temperatures a hundred metres away; it was the standard furnace pyrometer for fifty years.

The chart recorder

A chart recorder draws the reading against time on a moving paper chart.

The clockwork drum and circular chart

The barograph of The Barometer and the seismograph's drum (Seismographs) are the first recorders: the measuring element moves a pen arm, and a clock moves the paper.

  1. Drum recorder. A brass or tin drum about 9 cm across and 10 cm tall with a clock movement inside that turns it once a day or once a week. The chart wraps round it, held by a clip. The pen arm, 10–15 cm long, is moved by the Bourdon tube, capsule or bimetal through a light lever.
  2. Circular chart recorder. The commonest works recorder: a paper disc about 25–30 cm across turned once in 24 hours or 7 days by a clock or synchronous motor (Synchronous Motors and Converters). The pen moves outwards from the centre as the reading rises. Up to three pens of different colours on one chart.
  3. The chart. Because the pen swings in an arc, the time lines on the chart are not straight but arcs of the same radius as the pen arm. Print charts by Lithography and Offset Printing or from an engraved plate; the grid must match your pen arm exactly.
  4. The pen. A V-shaped nib of thin brass or steel folded so a drop of ink sits in it, or a fine glass capillary drawn from a small reservoir (Scientific Glassblowing and Glass-to-Metal Seals). The ink must not dry in a week: dissolve a strong dye in water with one-third glycerine (Ink, Soap). Touching lightly, it draws a fine, even line.
pressure in Bourdon tube moves the pen arm Pen arm swings in an arc Pen ink with glycerine Time lines arcs of the pen-arm radius, one every 2 hours Clock turns the chart once a day
Fig. 2 A circular chart recorder. The clock turns the paper disc once a day. A Bourdon tube moves the pen arm in an arc, so the time lines on the chart are printed as arcs of the same radius. The pen draws the pressure through the day.

The galvanometer recorder

A moving-coil meter (Measuring Electricity) has too little force to drag a pen across paper. Two old answers:

  • The dotting recorder. The pointer swings freely just above the chart. Every 15–30 seconds a chopper bar, worked by the clock, presses the pointer down onto an inked ribbon and the paper, printing a dot. A rotary switch can connect a new sensor before each dot, and the ribbon can carry several colours: a multi-point recorder printing six temperatures on one chart.
  • The optical recorder. A small mirror on the coil reflects a spot of light onto photographic paper (Photography). No friction at all, so it follows fast changes. Used for electrical faults and the first polarographs (Analytical Instruments).

The self-balancing (potentiometric) recorder

The best recorder for small electrical signals: exact to about 0.25 % of scale, with a strong pen.

  1. A slide-wire across a steady reference voltage gives a voltage that depends on where its slider sits.
  2. The input (from a thermocouple, a bridge, or a 4–20 mA signal across a 250 Ω resistor, which gives 1–5 V) is compared with the slider voltage. The difference goes to an amplifier (Amplifiers and Oscillators).
  3. The amplifier drives a small two-phase motor (The Electric Motor) that moves the slider, by a cord or a screw, in the direction that reduces the difference. When they match, the amplifier output falls to zero and the motor stops.
  4. The pen is fixed to the slider. Wherever the slider balances, the pen draws.
  5. The chart is a strip, usually 100–250 mm wide, fed from a roll by a sprocket that engages holes along its edges, at speeds from 20 mm an hour to 600 mm an hour for works, much faster for laboratories.
+ − M Input e.g. a thermocouple Amplifier amplifies the difference Balancing motor turns until the difference is zero Reference cell Carriage on a cord Slide-wire Pen chart moves roll driven by a synchronous motor, 20–600 mm an hour
Fig. 3 The self-balancing recorder. The input voltage is compared with the voltage from the slide-wire. Any difference is amplified and drives the motor, which moves the slider and pen until the two are equal. The chart moves steadily underneath.

Damp it so the pen moves across the full scale in about 1 second without overshooting: too little damping and the pen dithers; too much and it lags. Before electronic amplifiers, a galvanometer whose pointer was felt by a clock-driven mechanism every few seconds did the same job mechanically.

The data logger

Every works has a data logger already: the log sheet. An operator walks round every hour, writes each reading in its column, signs it and notes anything odd. Keep this habit even with recorders. A good log sheet has the normal range printed under each column heading, so a reading outside it is noticed when it is written.

Electronic data logger. A microcontroller with an analogue-to-digital converter reads each input in turn through a switch (multiplexer), adds the time from a quartz real-time clock (Quartz Crystals and Frequency Control), and writes the numbers to memory (Displays, Printers and Data Storage). Choose:

  • Resolution. A 10-bit converter divides the range into 1,024 steps (about 0.1 %); 12 bits, 4,096.
  • Interval. Once a minute is plenty for reservoirs and buildings; once a second for machines; faster only if you need it.
  • Memory. Four channels every minute for a year, 2 bytes each, is about 4.2 million bytes: a small memory card.
  • Power. A logger that sleeps between readings runs for a year on a few dry cells (Dry Cells and Electric Torches).

Earlier, printing data loggers scanned dozens of inputs with relays, measured each with a digital voltmeter and typed the numbers on paper. Once loggers report over wires or radio to a central The Computer, it becomes the supervisory control systems of modern plants (Telemetry and Remote Control, Networks and the Internet).

The control panel and control room

What goes on a panel

The mimic diagram

Paint the plant on the panel: pipes as coloured lines, tanks, pumps and valves as symbols, each with its instrument and its switch placed where it is in the process. An operator sees at a glance where the water or power goes and where the trouble is. Power stations paint the busbars and breakers this way.

RIVERLOW FILTERBLOCKED CHLORINELOW CHLORINEHIGH PUMP 1FAIL PUMP 2FAIL RESERVOIRLOW POWERFAIL River intake Pump 1 Filters Chlorinecontact tank Pump 2 Reservoir river level filter head loss chlorine recorder reservoir level running stopped start / stop start / stop acknowledge lamp test Alarm windows: flashing = new alarm, steady = acknowledged, dark = normal
Fig. 4 A waterworks control panel. Across the top, the alarm annunciator windows. Below, a mimic diagram of the works from river intake through filters and the chlorine contact tank to the reservoir, with indicators, recorders and pump switches placed where they act.

Building the panel

  1. Material. Early switchboards were slate or marble slabs, which do not burn or conduct. A good modern panel is 2–3 mm sheet steel, folded at the edges for stiffness, on an angle-iron frame (Sheet Metal and Rolling), earthed (Wiring and Electrical Safety). Hardwood is acceptable for low-voltage instrument panels.
  2. Heights. Indicators and recorders between 1.2 and 1.8 m from the floor, at eye level. Switches and controls between 0.8 and 1.4 m. The annunciator above, where it can be seen from the whole room.
  3. Rear access. Leave at least 80 cm behind the panel for wiring, with every wire labelled at both ends and on a drawing (Technical Drawing, Blueprints and Cyanotypes).
  4. Light. Even light without reflections on the dial glasses. Lamps behind the operator glare on the glass.
  5. Separate the dangerous from the room. Bring signals, not process pipes, into the control room. Never pipe steam, flammable gas, chlorine or acids into it (Chlorine and Bleach).

Alarms

An annunciator is a row of lettered glass windows, each lit from behind by a lamp, with a horn (Electric Bells, Buzzers and Alarms). Use the standard sequence, built from relays (The Relay Computer) or electronics:

  1. Alarm: the window flashes and the horn sounds.
  2. Acknowledge (button): the window goes steady, the horn stops.
  3. Return to normal: the window goes out (some systems need a reset button first).

Add a lamp test button that lights every window, and press it every shift. With first-out logic, the first window to trip flashes differently from those that follow, showing which fault started a cascade.

Make alarms fail safe. Wire each alarm contact so that it is closed when all is well and opens on alarm, and keep relays energised in the normal state. A broken wire or blown fuse then raises the alarm instead of hiding it.

Few, meaningful alarms. Every alarm must need an action by the operator. A panel that alarms constantly is ignored, and the one alarm that matters is missed.

Examples

Works The essential readings
Waterworks River level; raw and treated flow; filter head loss; chlorine left after contact; reservoir levels; pump running and pressure
Boiler house Steam pressure; drum water level (alarm low and high); feedwater flow; flue gas temperature; fuel (Boilers and Pressure Vessels)
Power station Frequency; voltage; current and power of each generator; breaker positions; turbine speed and bearing temperatures (The Generator, The Steam Turbine, Power Lines and Distribution)
Factory Furnace temperatures; air and water pressures; tank levels; motor currents

How to tell it worked

  • Calibrate zero and span of each loop: apply known pressure or temperature at two points (0 % and 100 %) and adjust. Then check 50 %.
  • Loop check. Inject 4, 12 and 20 mA with a calibrator and check that every indicator, recorder and alarm on the loop reads 0, 50 and 100 %.
  • Chart time. Mark the chart by hand with the time each morning. After a week the clock should be within 15 minutes.
  • Compare each panel reading with a local test gauge or thermometer once a month and log it.
  • Alarm test. Trip every alarm at least once a year from the real sensor, not just the lamp test.

Note Troubleshooting. Reading stuck at zero or below → broken wire, dead supply or transmitter (0 mA). That is what the live zero is for. Reading slowly drifts → blocked or leaking impulse line, air in a liquid line, water in an air line, or a thermocouple cold junction changing temperature. Pen skips or blots → ink too thin or nib dirty; clean the nib with warm water, add glycerine. Recorder pen dithers → amplifier gain too high or electrical noise; screen and earth the input cable at one end only (Interference, Screening and Earthing). Orifice flow reads high at low flow → zero drift is magnified by the square root; re-zero the differential transmitter with the line shut.

Dangers

Danger An instrument that fails can read normal. A stuck float, a frozen impulse line or a lamp that shows the command, not the valve's true position, can make operators act on false information while a vessel overfills or a boiler runs dry. At Three Mile Island in 1979, a panel lamp showed that a relief valve had been told to close, not that it had closed. Show the real state of important valves with a switch on the valve itself, and fit two independent sensors where a failure would kill.

Danger Control panels carry mains and often direct-current control supplies of 110 V or more. Isolate and lock off before working inside one, and test that it is dead (Wiring and Electrical Safety). Impulse lines carry the full process pressure and temperature: steam and hot water scald, and an opened line on a gas main can fill a room.

  • Mercury in old manometers, switches and thermometers is a poison (Mercury). Replace with other types where you can.
  • No instrument replaces the safety valve, the fuse or the low-water cut-off. Protection devices must work by themselves, without the control room (Pressure Vessels and Valves, Boilers and Pressure Vessels).

What this unlocks

A control room turns a collection of machines into a plant that a few people can run safely: the Power Lines and Distribution, Water Treatment for a Town, refineries and chemical works. Recorders feed Statistics and Probability and quality control. Signals in 4–20 mA and logged numbers lead directly to Robots and Automation and to plants run and watched by The Computers over Networks and the Internet.

How it was first done

Recording instruments are old: Christopher Wren designed a weather clock in the 1660s, and James Watt and John Southern drew the pressure inside a steam cylinder on paper with the steam engine indicator in the 1790s. The barograph and thermograph with clockwork drums spread in the 19th century, Richard Frères in Paris making them by the thousand from the 1880s. Hugh Longbourne Callendar built the first self-balancing temperature recorder in 1897. In the 1920s and 1930s, firms such as Leeds & Northrup, Foxboro, Taylor and Cambridge made potentiometric and multi-point recorders and pneumatic controllers, and central control rooms with mimic panels became normal in power stations. Electronic amplifiers replaced mechanical balancing in the 1940s and 1950s, electronic data loggers appeared in the late 1950s, and the 4–20 mA current loop became the international standard in the 1970s, which it remains alongside digital networks.