Cooling Towers and Spray Ponds

Every engine, power station, refrigerator and chemical works must throw away heat, and usually more heat than it turns into work. This chapter shows how to get rid of it with water and air. A cooling pond does it with nothing but surface area. A spray pond throws the water into the air. A cooling tower trickles it over timber or plastic fill while air is drawn through, either by the chimney effect of a tall hyperbolic shell or by a fan. It covers fill and drift eliminators, sizing, the water treatment that stops scale, rust and slime, and the Legionella bacteria that can spread from a dirty tower and kill.

Difficulty
●●●●●
Time
A week to dig and pipe a spray pond; a month to build a timber fan tower; two to three years for a large natural-draught tower
Steps from zero
44 prerequisites →

You need first

Heat ExchangersThe Steam Turbine

This unlocks

—
The full path from nothing — 44 steps before this one
  1. Fire
  2. Cordage and Rope
  3. Stone Tools
  4. Finding and Preparing Clay
  5. Finding and Identifying Ores
  6. Hunting and Trapping
  7. Basic Woodworking
  8. Charcoal
  9. Pottery
  10. The Kiln
  11. Hides and Leather
  12. Bricks
  13. Lime
  14. Mercury
  15. Lye and Potash
  16. The Wheel and Axle
  17. Firebrick and Refractories
  18. Glass
  19. Bellows
  20. The Lathe
  21. Gears
  22. Iron (the Bloomery)
  23. Copper Smelting
  24. Laboratory Glassware
  25. The Waterwheel
  26. Blacksmithing
  27. The Blast Furnace and Cast Iron
  28. Magnets
  29. The Barometer
  30. Sheet Metal and Rolling
  31. Steel
  32. The Steam Engine
  33. Copper Wire
  34. Machine Tools
  35. Boilers and Pressure Vessels
  36. The Generator
  37. The Electric Arc Furnace
  38. The Steam Turbine
  39. Calcium Carbide and Acetylene
  40. Welding
  41. Metal Pipes and Tubes
  42. Pressure and Vacuum Gauges
  43. Pressure Vessels and Valves
  44. Heat Exchangers
  45. Cooling Towers and Spray Ponds

Do them roughly in this order. See it on the tech tree →

Why it matters

No engine turns all its heat into work. A good The Steam Turbine power station turns about a third of its fuel's heat into electricity; the other two thirds leave in the condenser, where the exhaust steam is turned back to water (Heat Exchangers). So for every megawatt of electricity, about two megawatts of heat must go somewhere. The colder the condenser, the more power the turbine gives: every few degrees count.

The easiest place to dump it is a river or the sea. Cooling one megawatt of electricity's waste heat by a 10 °C rise in the water takes about 50 litres of water every second. A town's power station needs a river; a big one warms the river enough to kill its fish. Away from big rivers and coasts, the water must be cooled and used again. That is the job of ponds, spray ponds and cooling towers.

The same need arises wherever heat is made: the condensers of Ice and Refrigeration plants and big air conditioning systems (Ventilation and Air Conditioning), large engines (The Internal Combustion Engine, Gas Engines and Producer Gas), compressors (Bellows to Air Compressors), furnaces, steel mills and chemical works. A small plant can dump heat into air with a finned radiator (Heat Exchangers), but that needs a great deal of metal. Water and air together do it far more cheaply.

How it works

Evaporation does the work

When water evaporates, it takes heat with it: about 2,400 kJ for every kilogram, enough to cool 57 kg of water by 10 °C. That is why a wet cloth feels cold and a clay water jar keeps water cool (Ventilation and Air Conditioning). In a cooling tower, hot water is spread into drops and films with a huge surface, and air blows past. A little of the water evaporates and the rest cools. About four fifths of the heat leaves by evaporation; the rest warms the air.

So a tower uses up water: roughly 0.15% of the circulating water for every °C of cooling, about 1.5% for a 10 °C drop. For each megawatt of electricity, a power station's tower evaporates around 3 m³ an hour.

The wet-bulb temperature

Evaporation can cool water only down to the wet-bulb temperature: the reading of a thermometer whose bulb is wrapped in wet cloth and whirled in the air (Rain Gauges, Anemometers and Weather Stations). In dry air it is far below the ordinary (dry-bulb) temperature; in damp air, close to it. On a hot humid summer day of 32 °C the wet bulb may be 26 °C; in a desert at 40 °C it may be only 20 °C. Design for the hottest, dampest weeks of the year, or the plant loses power just when it is needed most.

Two terms describe a tower:

  • Range: how much it cools the water, hot in minus cold out. Usually 8–12 °C.
  • Approach: how close the cold water gets to the wet bulb. 4–8 °C is usual. Halving the approach roughly doubles the size of the tower, so do not chase a tiny approach.

Air, surface and time

Heat leaves through the water's surface, into air that keeps moving. A tower must therefore break the water up into drops or thin films over the largest possible area, keep it in the air stream as long as possible, and move about one kilogram of air for each kilogram of water. Wind alone is fickle. A chimney of warm, moist air (lighter than the outside air) draws air in steadily, as in Chimneys, Stoves and Heating. A fan does it in a smaller space.

What you need

Item Use See
Concrete or puddled clay Ponds and basins Mortar and Concrete, Finding and Preparing Clay, Dams and Reservoirs
Rot-resistant timber: cedar, larch, oak, or pine preserved with tar or creosote Frames, fill, eliminators Sawmills and Lumber, Rot, Woodworm and Termites
Pipes, valves Distribution Pipes, Plumbing and Aqueducts, Metal Pipes and Tubes
Centrifugal pumps Circulation Centrifugal Pumps and Fans
Large slow axial fan, motor, gearbox Fan towers The Electric Motor, Gears
Reinforced concrete and climbing formwork Natural-draught shells Reinforced Concrete
Wet- and dry-bulb thermometers Design and testing Rain Gauges, Anemometers and Weather Stations, The Thermometer
Chlorine, acid, test reagents Water treatment Chlorine and Bleach, Sulfuric Acid, Identifying Substances

The cooling pond

The simplest of all: a large, shallow pond. Hot water enters at one end; cool water is drawn from the other. Heat leaves the surface by evaporation, by radiation to the night sky and by wind.

  • Size: a pond loses roughly 30–50 watts per square metre for each °C that the water is above the temperature it would settle at on its own. So it needs about half to one hectare of surface for every megawatt of electricity a power station makes.
  • Depth: 1.5–3 m. Deeper ponds store heat and smooth out the day.
  • Layout: make the water travel the longest path, with baffle walls or islands so it does not take a short cut from inlet to outlet. Take the cold water from near the bottom.
  • Build: dig it like a reservoir, line it with puddled clay where the soil leaks (Dams and Reservoirs).

Ponds need no power and little care, and they hold enough water to ride out a breakdown. They suit a small plant on cheap flat land. For anything larger they take far too much land.

The spray pond

Throw the water up into the air as a spray over the pond, and it cools in seconds what a plain pond cools in hours. A spray pond needs about one twentieth to one thirtieth of the area of a plain pond.

PlanSwirl nozzleSection hotcoldlouvred fence; nozzles 3–4 m apart from above: water enterssideways and spins mouth25–40 mmhollow cone of drops hot water in, 0.5–0.7 bar sprays rise 2–3 m and cool as they fall wind louvred fence pond 1.2–1.5 m deep cold
Fig. 1 A spray pond. Hot water from the condenser is pumped through buried pipes to rows of nozzles that throw it up 2–3 m in cone-shaped sprays; it cools as it falls and is drawn off cold at the far end. A louvred fence round the pond catches wind-blown spray. Inset: the swirl nozzle in section; water enters sideways, spins, and leaves the mouth as a hollow cone of drops.
  1. The pond: concrete or clay-lined, 1.2–1.5 m deep, with a sump and screen at the outlet end.
  2. Pipes: a header from the pump running along the pond, with branch pipes across it, laid on piers just under the water or above it, sloping so they drain.
  3. Nozzles: on short risers, 3–4 m apart in each direction. Keep the outer rows at least 6–8 m from the edge, more on the side of the prevailing wind.
  4. Fence: a louvred fence of slanted boards 2–3 m high round the pond catches spray blown by the wind, which would otherwise be lost and would wet the neighbours with warm water.

The spray nozzle. Cast in bronze or iron. Water enters a short round chamber sideways, so it spins, and leaves through a round mouth 25–40 mm across, opening into a hollow cone of fine drops. Feed it at about 0.5–0.7 bar (5–7 m of head); higher pressure makes finer drops that cool better but blow away. A nozzle of this size passes 5–10 m³ an hour.

Sizing. As a starting figure, allow about 1–2 m² of pond for each cubic metre of water per hour, about 10–15 m² per nozzle at the spacing above, and check it once it is running. A spray pond cools the water by 5–8 °C per pass, and gets within 6–10 °C of the wet bulb. For more cooling, send the water through two banks of nozzles in turn.

Spray ponds were used for power stations, ice works and large engines from the 1900s. They lose more water to wind than a tower and cannot be built near roads or houses, but they are cheap and need only a pump.

The cooling tower

A tower puts the spray or the film of water inside a casing, with air drawn through it on purpose. It fits a much bigger load into a small space.

Fill

The fill is the heart of a tower: a stack of surfaces that break the water up and slow its fall.

  • Splash fill: rows of horizontal timber slats, about 1 × 5 cm in section, about 10–20 cm apart across, the rows 20–30 cm apart in height, each row staggered from the one below. Water falling on a slat splashes into drops, which fall to the next. Splash fill passes dirty water and silt without clogging. It needs depth, 4–8 m of it in a big tower. Fireclay tiles and bricks laid in an open checker work the same way (Bricks), are fireproof and last for decades, but are heavy.
  • Film fill: thin sheets hung on edge 2–2.5 cm apart, corrugated or ribbed, over which the water runs as a thin film. It packs far more surface into the same volume, so 1–1.5 m of it does the work of 5 m of splash fill. But its narrow passages clog with silt, scale and slime. Make it from thin planed boards, or from sheets of plastic (Petrochemicals and Modern Plastics).

Good fill carries the water down evenly, with no dry patches and no streams pouring straight through. Look up into it with a lamp while it runs: you should see an even rain or a glistening, unbroken film everywhere.

Distribution and eliminators

  • Distribution: in a counterflow tower, where the air rises against the falling water, a pipe grid sprays water downward over the fill through nozzles about 0.6–1 m apart. In a crossflow tower, where air enters the sides and crosses the falling water, the water flows into an open hot-water basin on top, with holes or small nozzles in its floor; it works by gravity and is easy to inspect.
  • Drift eliminators: the leaving air carries fine drops, called drift. An eliminator above the sprays is a set of bent blades, a zigzag or chevron of 2–3 passes, through which the air must turn sharply; the drops cannot turn and hit the blades. Make them of wooden slats set at 45° in two opposite rows, or of bent sheet metal or plastic. A good eliminator holds drift to under 0.02% of the circulating water. It saves water, and it stops the tower from spraying bacteria over its neighbours (below).

Natural-draught towers

The great grey towers of power stations are chimneys. The air inside, warm and laden with moisture, is lighter than the air outside, so it rises, drawing fresh air in through the open base.

100–200 m tall warm moist plume concrete shell 15–25 cm thick, hyperbolic drift eliminators hot water from condenser sprays fill timber slats air in air in cold water basin to condenser warm air rises
Fig. 2 A natural-draught cooling tower in section. Air enters round the open base between slanting legs, passes up through the fill, where it meets the falling hot water, then rises through the sprays and drift eliminators and out of the top of the tall concrete shell as a warm plume. Cooled water collects in the basin and returns to the condenser.
  • The draught is small: it is the height times the difference in density. A tower 100 m tall with air inside about 4% lighter gives only 40–60 pascals, the pressure of a few millimetres of water. So the fill and eliminators must offer little resistance, and the tower must be tall.
  • The shell is a hyperbolic shape, narrowing to a waist about four fifths of the way up and flaring slightly at the top. That doubly curved shell is very stiff for its thickness, so it can be very thin: reinforced concrete 15–25 cm thick over most of its height, thickening near the base (Reinforced Concrete). It stands on a ring of slanting columns that leave the base open for the air. It is built ring by ring with climbing formwork.
  • Sizes: towers for large power stations are 100–200 m tall and 80–120 m across at the base, each cooling 500–1,000 MW of heat with no fan at all.

A natural-draught tower uses no power and lasts 50 years or more, but it is a huge work of concrete. Towers have collapsed in strong winds when grouped too closely, as at Ferrybridge in England in 1965, when three of eight fell in a gale. Leave space between them, and design for the wind.

Small natural-draught towers of timber, 10–20 m tall, were built for mines and factories before fans were common, but their weak draught makes them big for their duty. For a small plant, use a fan.

Fan towers

A mechanical-draught tower uses a fan. In the induced-draught type, the fan sits on top in a short flared fan stack and pulls air up through the tower; this is the usual and best arrangement, because the warm, wet air is thrown high and does not drift back into the inlets. In the forced-draught type, the fan at the bottom blows air in.

fan stack warm wet air out fan, 1.5–1.8 m motor and gearbox drift eliminators hot water in sprays fill splash or film air in louvres make-up float valve bleed-off to drain pump, then to condenser Splash fill: staggered slats Film fill: sheets 2–2.5 cm apart Eliminator: air must turn twice dropshit theblades
Fig. 3 A small induced-draught counterflow cooling tower in section. Hot water from the condenser is sprayed downward over the fill; air drawn in through the louvres at the bottom rises through the fill and the drift eliminators and is blown out of the fan stack by the fan. Cold water collects in the basin, with a float valve to replace what evaporates and an overflow to bleed off salty water. Inset: splash fill of staggered slats, film fill of closely spaced sheets, and a two-pass eliminator.

Example: a tower for 300 kW of heat, enough for a small steam plant, a large ice works or a hospital's air conditioning.

  1. Water flow. For a range of 8 °C: 300 kW ÷ (4.19 × 8) = 9 kg/s, about 32 m³ an hour.
  2. Plan area. A counterflow tower with good fill handles about 10 m³ of water per hour per square metre, so about 3.2 m²: a box 1.8 × 1.8 m inside.
  3. Air. About as much air as water by weight: 9 kg/s, about 7.5 m³/s. Through 3.2 m², that is about 2.3 m/s, a good speed for fill and eliminators.
  4. Fan. An axial fan about 1.5–1.8 m across (Ventilation and Air Conditioning), slow-running so it is quiet, against about 150 Pa of resistance: a 2–3 kW motor, through a belt or a gearbox (Belts, Chains and Power Transmission). Blade tips run in a flared stack with only 1–2 cm of clearance.
  5. Fill. 1.2 m of film fill, or 3–4 m of splash fill, which makes the tower taller.
  6. Water use. Evaporation about 0.4 m³ an hour. Add bleed-off (below): make-up water about 0.5 m³ an hour, about 12 m³ a day.

Building it.

  1. Basin: a concrete tank 0.5–0.6 m deep, a little bigger than the tower, its floor sloping to a sump with a screen and a drain. Set a float valve for make-up water (Pipes, Plumbing and Aqueducts) and an overflow at the working level.
  2. Frame: posts and braces of rot-resistant timber (Timber Framing and Log Building), bolted with galvanised or bronze bolts. Iron nails rust away in a year in the wet.
  3. Casing: boards or corrugated sheet on the frame, with the lowest 0.8–1 m left open on all sides for air, fitted with louvres (slanted boards) that keep the water in and the sunlight off the basin.
  4. Fill above the louvres; spray pipes above the fill, with nozzles at 0.6 m spacing pointing down; eliminators above the sprays; a fan deck and stack on top, with a strong guard.
  5. Pipework: hot water from the condenser to the spray pipes; cold water from the sump through the circulating pump (Centrifugal Pumps and Fans) back to the condenser. Put the pump below the basin level, so it is always full.

Keeping the water right

As water evaporates, everything dissolved in it stays behind and grows stronger. Dust from the air, sunlight and warmth add slime and algae. Without care, a tower scales up, rusts its pipes and grows germs within weeks.

Bleed-off and cycles. Let a steady trickle of tower water run to waste, the blowdown or bleed-off, and replace it with fresh. The ratio of the salt in the tower water to the salt in the make-up is the cycles of concentration; keep it at 3–5. Measure it by chloride, which never settles out: titrate a sample of each with silver nitrate (Silver Nitrate and Silver Salts, Identifying Substances), and divide. Blowdown needed = evaporation ÷ (cycles − 1). At 4 cycles and 0.4 m³/h of evaporation, bleed 0.13 m³/h.

Scale. Lime scale on the hot condenser tubes chokes heat flow (Water Softening and Ion Exchange explains why). Keep it off by enough bleed-off; by a small dose of sulfuric acid to hold the pH at about 7–7.5; or by softening the make-up water.

Corrosion. Warm, aerated, salty water eats iron. Keep the pH above about 7, use bronze, copper or stainless steel for condenser tubes, and coat steelwork. Old plants used chromate to stop rust: it works but is poisonous and causes cancer. Do not use it.

Slime and algae. Keep sunlight off the water with covers and louvres. Dose chlorine to keep about 0.5–1 mg/L of free chlorine in the basin water, tested daily (Chlorine and Bleach, Water Treatment for a Town). Too much chlorine slowly rots timber fill.

Cleaning. At least twice a year, and before starting a tower that has stood idle: shut it down, chlorinate strongly, drain it, scrape the sludge out of the basin and fill, wash it down, refill and chlorinate again.

How to tell it worked

  • Range and approach: with the plant at full load, measure hot water in, cold water out, and the wet bulb of the air entering. The approach should be what you designed, usually 4–8 °C.
  • Even flow: no dry patches in the fill, no jets pouring through, no water thrown out of the louvres.
  • Plume: on a cool day a white plume rises straight up. Drops falling from it like rain mean the eliminators are damaged.
  • Water: clear, no green, no slime on a finger rubbed along the basin wall, no smell. Cycles of concentration steady between 3 and 5. Germ counts low (Culturing Microbes).
  • Condenser: the turbine's vacuum stays good in hot weather (The Steam Turbine).

Note Troubleshooting. Cold water too warm → too little air (fan belt slipping, louvres blocked with leaves, eliminators fouled), uneven distribution (blocked nozzles), fill clogged with scale or slime, or warm wet air from the fan being drawn back into the inlets. Water level falls fast → drift through damaged eliminators, a leak in the basin, or the bleed-off set too high. White scale on fill and tubes → too many cycles; bleed more or dose acid. Green water, slimy fill → sunlight and too little chlorine; cover, clean and dose. Fill collapses in winter → ice. In freezing weather, run fans slower or backwards for a few minutes, or bypass the fill and let the water fall straight into the basin.

Dangers

Danger Legionnaires' disease. The bacterium Legionella lives in warm water at 20–45 °C, in slime and sludge, exactly what a neglected tower offers. Drift drops carrying it can blow more than a kilometre. Breathed in, they cause a severe pneumonia that kills about one in ten of those it strikes, more among the old, smokers and the sick. Keep eliminators whole, chlorinate continuously, clean twice a year, never leave water standing in a tower or its pipes, and site towers away from windows, air intakes, hospitals and crowds. Wear a close-fitting dust mask or respirator when cleaning or entering a tower. When pneumonia cases cluster near a tower, shut it down and disinfect it at once.

  • Fans: a big fan turns slowly enough to seem harmless and will cut off a limb. Lock off and tag the motor switch before going near it (Wiring and Electrical Safety).
  • Heights and slippery timber: guard rails on the fan deck; never work alone up there.
  • Confined spaces: a basin, sump or tower casing can collect chlorine gas or lack air. Ventilate before entry and keep a person outside.
  • Fire: dry timber towers, stopped for repair, burn fiercely; welding sparks have set many alight. Keep the fill wet or have hoses ready when welding.
  • Chemicals: acids and chlorine burn skin and eyes; never mix acid and chlorine solutions, which gives off chlorine gas.
  • Drowning: fence ponds and cover basins.

What this unlocks

Towers let power stations be built away from big rivers and close to fuel or to the towns they serve (Power Lines and Distribution). They let refrigeration and air conditioning run in hot countries, and they let steel mills, chemical works and paper mills reuse their water a hundred times over instead of draining rivers. A dry cooling tower, a natural-draught shell full of finned radiators, uses no water at all and suits deserts, at the cost of a lot of metal and a few percent of power (Heat Exchangers). A heat pump can take the same waste heat and lift it for heating towns (Heat Pumps and District Heating).

How it was first done

Factories and engine houses cooled their condenser water in ponds and open channels from the early days of steam. Spray ponds and timber towers with slatted fill and louvred sides appeared in the late 19th century, as electric power stations and ice works grew. The first hyperbolic cooling tower was built in 1918 at the Emma state coal mine at Heerlen in the Netherlands, designed by the engineers Frederik van Iterson and Gerard Kuypers, who had patented the shape for its strength and draught. Britain's first followed at the Lister Drive power station in Liverpool in the 1920s. Fan towers spread through the 20th century with cheap electric motors. In 1976 an outbreak of pneumonia at a convention of the American Legion in a Philadelphia hotel killed 34 people; the bacterium, named Legionella, was found in 1977, and the hotel's air conditioning cooling tower was the likely source. Outbreaks from cooling towers since, such as that of Murcia in Spain in 2001 with several hundred cases, made regular cleaning and disinfection law in many countries.