Part 13 · Electricity
Motor Starters, Contactors and Protection
A big motor must be started gently, stopped instantly from anywhere, and switched off before it burns itself out, and nobody must be killed by a fault in a wet place. How to build the contactor (a switch worked by an electromagnet), the push-button starter that will not restart by itself, the overload relay, the star-delta and reversing starters, interlocks and emergency stops, and the residual-current device that cuts the power when current leaks through a person.
- Difficulty
- ●●●●●
- Time
- A few days for a contactor and push-button starter; a week for a star-delta or reversing starter; one to two weeks to build and test a residual-current device
- Steps from zero
- 25 prerequisites →
This unlocks
Power Electronics and Motor DrivesThe full path from nothing — 25 steps before this one
- Fire
- Cordage and Rope
- Stone Tools
- Finding and Preparing Clay
- Finding and Identifying Ores
- Hunting and Trapping
- Basic Woodworking
- Charcoal
- Pottery
- Hides and Leather
- Fermentation
- The Wheel and Axle
- Bellows
- Gears
- Copper Smelting
- Iron (the Bloomery)
- The Waterwheel
- Blacksmithing
- The Battery
- Magnets
- Copper Wire
- The Electromagnet
- The Generator
- The Electric Motor
- Wiring and Electrical Safety
- Motor Starters, Contactors and Protection
Do them roughly in this order. See it on the tech tree →
Why it matters
An The Electric Motor on a plain knife switch is dangerous three ways. Its starting surge dims every lamp on the line and burns switch contacts. If it jams, it cooks its windings too slowly for a fuse to notice. And if the power fails and comes back, it restarts by itself, perhaps with someone's hand in the saw.
A contactor lets a push-button switch a big motor from a safe distance; a starter built round it will not restart after a power cut and starts big motors gently; an overload relay stops a motor before it cooks; emergency stops and interlocks stop machinery the instant anyone needs it. Together they make Machine Tools, Planers, Thicknessers and Woodworking Machines, Sawmills and Lumber, pumps, Cranes and Lifting, Lifts, Hoists and Mine Winding and every workshop motor safe to run.
The last device, the residual-current device, guards people rather than motors. In bathrooms, dairies, laundries and building sites, wet skin lets enough current through a body to kill long before any fuse notices. The residual-current device cuts the power in a few hundredths of a second when it sees a leak as small as 30 thousandths of an ampere — less than the current that stops a heart (Wiring and Electrical Safety).
How it works
Why motors need gentle starts
A motor standing still makes no back-voltage, so its current is limited only by the resistance and reactance of its windings (The Electric Motor). An induction motor draws six to eight times its full-load current for the few seconds it takes to reach speed. A 7.5 kW motor that runs at 15 A on 400 V draws about 100 A at the instant of starting. Small motors can take this; big ones, or weak supplies like a village The Generator, cannot.
The holding circuit
The heart of every starter is a trick with a relay. The contactor has, besides its heavy main contacts, a small auxiliary contact that closes with them. Wire that contact across the START button. Press START: the coil pulls in, the auxiliary contact closes and keeps the coil fed after you let go. Press STOP (a button whose contacts are normally closed and open when pressed): the coil loses current and drops out, and stays out.
The same trick gives no-volt protection for free: if the supply fails, the coil drops out and stays out. When the power returns, nothing starts until someone presses START.
Fail safe
Every stopping device — STOP button, emergency stop, overload contact, guard switch — is wired in series in the coil circuit and works by opening it. A broken wire, a burnt-out coil or a dead supply then also stops the machine. Never build a stop that works by closing a circuit to "turn off" a motor: a broken wire would leave you with no stop at all.
What you need
| Item | Notes |
|---|---|
| Soft iron sheet 0.35–0.5 mm, varnished | Laminated cores for AC coils (The Transformer) |
| Copper wire, enamelled or cotton-covered | Coils: 0.2–0.4 mm; main wiring sized for the motor (Copper Wire) |
| Copper bar and strip | Contacts and bridges |
| Silver | Facing for contacts, a few grams (Gold and Silver) |
| Slate, soapstone, fired porcelain, hardwood boiled in wax | Bases and insulating carriers (Stoneware and Porcelain) |
| Steel springs | Return and contact-pressure springs (Springs) |
| Brass and bimetal strip | Overload relays (Thermostats and Automatic Control) |
| Sheet steel boxes, earthed | Enclosures with lockable doors (Sheet Metal and Rolling) |
| Ammeter, voltmeter, test resistors | Measuring Electricity |
Where to find it
Slate splits into flat, stiff sheets; good switchboard slate rings when tapped and has no shiny veins of ore, which conduct. Soapstone carves with a knife for small insulating blocks. Mica splits into thin sheets from pegmatite veins. Hardwood carriers must be boiled in wax or soaked in lac so they do not take up damp.
The contactor
A contactor is a heavy-duty relay: a coil that, when fed, pulls an armature carrying a row of heavy contacts that close the motor circuit.
Build it
- Core. Stack 0.5 mm iron sheets into an E-shape about 4 × 4 cm, centre leg 1.2 cm wide, stack 2 cm thick, with a matching I-shaped armature.
- Shading rings. On AC the pull falls to zero twice each cycle, and the armature chatters. Press a closed ring of thick copper (2 × 3 mm) into a slot across the face of each outer leg: current induced in it keeps some magnetism alive while the main field passes zero.
- Coil. For a 230 V AC coil on this core, wind about 4,500 turns of 0.15 mm enamelled wire on a former of varnished card. For a coil fed from a 24 V control transformer (safer for push-button wiring), about 470 turns of 0.5 mm. Try it: it should pull the armature in firmly at 85% of its rated voltage and let go when the voltage falls to about half.
- Moving bar and bridges. On an insulating bar fixed to the armature, mount one copper bridge per pole (about 3 × 10 × 40 mm) on a light pressure spring. Each bridge closes two gaps in series between a pair of fixed contacts on the slate base, so each gap breaks only half the voltage.
- Silver faces. Silver-solder (Soldering and Brazing) a disc of silver 6 mm across, 1 mm thick on every contact face. Copper oxide resists and overheats; silver oxide still conducts.
- Gap and wipe. Open gap 3–4 mm per break for 400 V. After the contacts touch, the armature should travel 2–3 mm more, compressing the pressure springs; this "wipe" keeps pressure on as the faces wear.
- Return springs strong enough to open crisply, weak enough that the coil seals in fully.
- Arc plates. Beside each break, a stack of 6–8 thin steel plates 2–3 mm apart on mica spacers splits the arc into short pieces that go out. For DC, a blowout coil in series pushes the arc into the plates.
- Auxiliary contact. A small normally open contact worked by the same bar.
Size: contacts like these carry about 16 A continuously and switch a motor of about 5 kW at 400 V three-phase.
Good contactor: one clean clack, quiet while held, opens instantly. Bad: hums (shading ring cracked, faces not flat), chatters (coil too weak), contacts blackened within weeks (too little pressure, no silver).
Push buttons
A start button is a spring-returned plunger whose brass bridge closes two contacts, coloured green and shrouded against accidental presses. A stop button's contacts are held closed by the spring and pushed apart when pressed; it is red and stands proud. Mount both in an earthed metal box, and run the coil circuit at 24–48 V from a small The Transformer where you can.
The direct-on-line starter
The simplest motor starter, for motors that can stand full-voltage starting — up to about 5–7 kW on a strong supply.
- Isolator first: a lockable hand switch that cuts all live wires to the whole starter (Wiring and Electrical Safety).
- Fuses in each line, sized to carry the starting surge but blow on a short circuit: about two to three times the motor's running current, using slow fuse wire.
- Contactor main contacts.
- Overload relay (below), one heater in each line.
- Control circuit: supply → STOP (closed) → EMERGENCY STOP (closed) → overload contact (closed) → START (open), with the auxiliary contact across START → coil → back to supply.
The overload relay
Fuses protect the wiring against short circuits; they cannot protect a motor, because a fuse fine enough to blow on a 20% overload would also blow every time the motor starts. The overload relay waits: it lets a starting surge pass for several seconds but trips a long overload within minutes.
- Heater. For each line, a few turns of nichrome or iron strip carrying the motor current, wound round a bimetal strip of brass and iron riveted together (Thermostats and Automatic Control). Small motors: the current goes through the bimetal itself.
- Trip bar. The three bimetals bend as they warm and push a common insulated bar. When any one bends far enough, the bar knocks open a small normally closed contact in the contactor coil circuit.
- Single-phasing. If one line of a three-phase supply fails, the motor keeps running on two and those two carry far more current. Arrange the bar so that if one bimetal stays cold while the others bend, it trips sooner.
- Hand reset. After tripping, the contact must be reset by hand with a button, so the motor cannot restart by itself as the strip cools.
- Set with an adjustable screw stop, by test: run the motor's full-load current through the heaters from a low-voltage transformer, and adjust until it never trips at 105% of full-load current, trips within about two hours at 120%, and trips within about 4 minutes at 150%. At six times full-load current (a stalled motor) it should trip in 5–20 seconds.
An older type pulls an iron plunger against an oil dashpot, for large motors with long starts.
Starting big motors gently
Star-delta
A three-phase induction motor has three windings. Connected in delta (each winding across two lines), each gets the full line voltage. Connected in star (one end of each joined together), each gets only 0.58 of it. Start in star and the motor draws only a third of the direct-on-line current — and gives a third of the starting turning force, enough for fans, centrifugal pumps, saws and machine tools started unloaded.
- The motor must be wound to run in delta on your line voltage, with all six winding ends brought out to the terminal box.
- Three contactors: main (feeds one end of each winding), star (joins the other ends together), delta (connects those other ends to the lines in rotation).
- Interlock star and delta, so they can never close together, which would be a dead short: a lever between the two armatures (mechanical), and a normally closed auxiliary contact of each in the other's coil circuit (electrical).
- A timer switches from star to delta after 5–15 seconds, when the motor is at about 80% of speed: a dashpot (a piston leaking air or oil through a small hole), clockwork, or a small synchronous motor turning a cam.
Other methods
- Direct current motors start through a stepped resistance (The Electric Motor). Add a no-volt coil that holds the starter arm at the running position against a spring: if the power fails, it lets go and the spring throws the arm back to OFF.
- Slip-ring motors start with resistances in the rotor circuit, cut out step by step: high starting force at low current, for Cranes and Lifting and mills.
- Autotransformer starters start on a 50–80% tap of a three-phase The Transformer.
The reversing starter
Swapping any two of the three lines to an induction motor makes it run backwards. Use two contactors, FORWARD and REVERSE, the second with two lines crossed. Interlock them mechanically and electrically exactly as for star-delta. Add limit switches at the ends of travel of hoists, cranes and machine tables, each a normally closed contact in the coil circuit of the contactor that drives towards it.
Emergency stops and interlocks
The emergency stop
A large red mushroom-headed button on a yellow background, within reach of every place a person works at the machine — and on long machines, a pull-cord along its length.
- It works by forcing its contacts apart with the plunger itself, never by letting a spring open them: a welded or stuck contact is then broken open by your blow.
- It latches down when struck, and must be twisted or pulled to release.
- Releasing it must not restart the machine. The contactor has dropped out; only START brings it back.
- It cuts the coil circuit of every contactor driving dangerous motion. On a machine with a heavy flywheel or a long run-down, add a brake that is applied by a spring and released by power.
Guards and interlocks
A guard interlock is a switch worked by the guard itself (a cam, a tongue entering a slot, or a hinge), wired as a normally closed contact in the coil circuit, so the machine cannot run with the guard open. Where the machine runs on after switching off, a solenoid bolt must also lock the guard shut until it stops.
Lock off before you reach in
Before anyone works on a machine, they open its isolator and put their own padlock on it; three workers, three padlocks. Then prove it dead: press START, and test with a voltmeter at the motor terminals.
The residual-current device
How it works
In a healthy circuit, every bit of current that goes out on the live wire comes back on the neutral. If some of it leaks to earth — through a damaged cable, a wet appliance, or a person — the two are no longer equal.
Pass both the live and the neutral wire through a ring of iron. Their currents flow opposite ways, so their magnetic fields cancel exactly, and the ring stays unmagnetised. When some current leaks away, the difference magnetises the ring. A third coil wound on the ring — the sense coil — picks up that difference and fires a trip that opens the circuit.
Build it
- The ring must respond to a tiny current. Best is a nickel–iron alloy (50–80% nickel, Nickel and Cobalt); otherwise the softest pure iron. Wind strip 0.1–0.2 mm thick and 10 mm wide into a ring 3–4 cm across, anneal it in charcoal at red heat, cool slowly, and never bend it after.
- Primaries. Pass the live and the neutral through the ring together, or wind each 4–5 turns round it in exactly the same direction, side by side, as a twisted pair.
- Sense coil. Wind 500–1,000 turns of 0.1 mm wire evenly on the ring.
- Trip relay. The sense coil gives only thousandths of a watt, so use a polarised relay: a light armature held to its pole by a permanent magnet (Magnets) against a spring, adjusted so it only just holds. The sense coil's pulse weakens the magnet, the spring wins, and the armature knocks the latch of a spring-loaded switch that opens both live and neutral. A transistor amplifier (Semiconductors and the Transistor) allows a plain-iron ring and a simpler trip.
- Test button. A push-button that connects a resistor from the live wire after the ring to the neutral wire before it, so a deliberate leak passes. For a 30 mA device on 230 V, about 3.9 kΩ (about 60 mA, twice the rating); on 110 V, 1.8 kΩ.
Set and test it
Use resistors from live (on the load side) to earth to make known leaks. A good residual-current device for protecting people:
| Leak | Must |
|---|---|
| 15 mA | Not trip |
| 30 mA | Trip within 0.3 seconds |
| 150 mA | Trip within 0.04 seconds |
Time it with a synchronous clock motor fed through the device: the angle it turns before the trip stops it gives the time. Press the test button every month; a stuck device is worse than none, because people trust it.
What it does and does not do
- It saves lives when someone touches a live part while standing on wet ground, or holds a faulty tool in a wet hand. Fit one on every socket circuit in bathrooms, kitchens, laundries, dairies, outdoors and on building sites, and on Electric Fences mains supplies and washing machines.
- It does not protect someone who touches live and neutral at the same time, standing on something dry: the current goes out and comes back through the same ring. It does not replace fuses, which guard against overloads and short circuits, or the earth wire, which it needs to work at its best.
- A 300 mA device on the main supply of a building guards against fires started by slow leaks to earth in damp walls.
How to tell it worked
- Contactor: pulls in at 85% voltage, drops out between 40% and 60%; quiet when held; contacts warm, not hot, after an hour at full load.
- Starter: press START, the motor runs; let go, it keeps running; press STOP or the emergency stop, it stops. Switch the supply off and on with the motor running: it stays stopped.
- Overload: with the motor shaft braked to give 150% current, it trips within a few minutes and will not restart until reset.
- Star-delta: an ammeter in one line shows a starting kick about a third of a direct-on-line start, a smaller second kick at changeover, then normal running current.
- Residual-current device: trips on the test button every time, and on a 30 mA test leak within a third of a second.
Note Troubleshooting. Contactor drops out when the motor starts → the supply sags under the starting surge. Thicker supply wires, or star-delta starting. Motor starts and stops at once → holding contact not wired across START, or not closing. Overload trips on every start → setting too low, or the start too long; use star-delta, or a slower relay. Contactor welds shut → contacts too small, pressure too low, or switched onto a short. Fit bigger silver faces and check the fuses. Residual-current device trips for no reason → genuine small leaks from many damp appliances adding up; split circuits between devices. Or a neutral touching earth beyond the device. Residual-current device will not trip on test → relay latch stuck or ring too weak. Do not use it until fixed.
Dangers
Danger Control circuits lie. A contactor that has dropped out does not make a motor safe to touch: the wires above it are still live, and a stuck contact or a careless hand on START can bring it back. Only an open, padlocked isolator, tested dead, makes a machine safe to work on.
Danger Test residual-current devices with resistors, never with yourself or an animal. A device that is slow or set too high will let a test current kill.
- Arc flash. Opening a contactor or switch under heavy current draws an arc that can melt copper and burn eyes and skin. Keep covers on, and never open the enclosure of a working starter.
- Wrong-way connections. A star-delta starter wired with the wrong winding ends, or with a broken interlock, makes a dead short with a bang and molten metal. Check every connection with a lamp and battery before connecting the supply.
- Machinery that moves by itself. Hoists, presses and saws with stored energy — weights, springs, flywheels — can move even with the power off. Block them mechanically before reaching in.
What this unlocks
- Safe motor-driven workshops: Machine Tools, Sawmills and Lumber, pumps and Textile Machinery with stops at every station.
- Lifts, hoists and cranes with limit switches and reversing starters (Lifts, Hoists and Mine Winding, Cranes and Lifting).
- Automatic control: contactors worked by Thermostats and Automatic Control, float switches (Photocells and Sensors) and timers run pumps, kilns (Electric Kilns and Furnaces) and heaters unattended, and lead on to Process Controllers and Control Valves and Robots and Automation.
- Safer homes and farms: residual-current devices on every wet-area circuit (Wiring and Electrical Safety, Power Lines and Distribution).
How it was first done
By the 1890s DC faceplate starters carried a no-volt release coil. Push-button contactors came into use for large motors and lifts around 1900–1910, as AC induction motors spread after the work of Nikola Tesla and of Mikhail Dolivo-Dobrovolsky, who built the first practical three-phase squirrel-cage motors at AEG in Berlin around 1889. Star-delta starting was in use early in the 20th century, and bimetal overload relays became standard in the 1920s and 1930s.
The residual-current principle was probably first patented in Germany in the late 1920s, but devices sensitive enough to protect people came after the Second World War: in Austria, notably through Gottfried Biegelmeier, and in the United States through Charles Dalziel, who had measured how much current a person can let go of and invented the ground-fault interrupter in the early 1960s. By the end of the century they were required on bathroom and outdoor circuits in most countries.