◆ Rebuild

Part 13 · Electricity

Wiring and Electrical Safety

How to carry electricity from a generator to lamps, sockets and machines without starting fires or killing anyone — choosing wire sizes, insulating and joining wire, fuses and breakers, earthing, switches and sockets, safe working habits, and first aid for electric shock.

Difficulty
●●●●●
Time
A day or two to wire a workshop once you have wire, insulators and fuses; a lifetime of good habits
Steps from zero
20 prerequisites →

You need first

Copper WireThe Generator

This unlocks

Insulators, Cables and Electrical FittingsElectric Kettles, Irons, Heaters and CookersFans, Vacuum Cleaners and Washing MachinesMotor Starters, Contactors and ProtectionPower Lines and Distribution
The full path from nothing — 20 steps before this one
  1. Fire
  2. Cordage and Rope
  3. Stone Tools
  4. Finding and Preparing Clay
  5. Finding and Identifying Ores
  6. Hunting and Trapping
  7. Basic Woodworking
  8. Charcoal
  9. Pottery
  10. Hides and Leather
  11. The Wheel and Axle
  12. Bellows
  13. Gears
  14. Copper Smelting
  15. Iron (the Bloomery)
  16. The Waterwheel
  17. Blacksmithing
  18. Magnets
  19. Copper Wire
  20. The Generator
  21. Wiring and Electrical Safety

Do them roughly in this order. See it on the tech tree →

Why it matters

A The Generator on a stream is a wonderful thing until the wire to the house glows red inside a wall, or a child touches the metal case of a pump whose winding has rubbed through. Electricity kills quietly and burns houses down from the inside. Every place that got electric light in the 1880s learned this the hard way, and the rules in this chapter were written by fire insurers and engineers after those losses.

Good wiring means four things: wires thick enough that they stay cool; insulation and spacing so current goes only where it should; fuses or breakers that cut the power before a fault becomes a fire; and earthing, so that a fault blows the fuse instead of making something deadly to touch. Add careful habits and first aid, and electricity becomes as safe as fire in a good stove. The same rules apply to The Telegraph and The Telephone lines, to The Transformers, and to the Power Lines and Distribution that grows out of them.

How it works

What a shock does

Current through the body is what hurts, and it is the path through the chest that kills. Roughly, for alternating current of 50–60 Hz flowing for a second or so from hand to hand or hand to feet:

Current Effect
1 mA (one thousandth of an amp) A tingle
5–10 mA Painful; you can still let go
10–20 mA Muscles clamp; you cannot let go of the wire
30–50 mA Breathing becomes hard; the heart may start to quiver instead of beating (fibrillation)
100 mA and more The heart very likely fibrillates — death within minutes without help

How much current flows depends on the voltage and on the resistance of the body (see Measuring Electricity). Dry, thick-skinned hands may resist 10,000–100,000 ohms; wet or sweaty skin, a cut, or standing in water drops it to 1,000 ohms or less. At 100 V through wet skin that is 100 mA — enough to kill. So:

  • Below about 25 V AC (or 50 V DC): safe to touch, even with damp hands.
  • 25–50 V AC: dangerous when wet.
  • Above 50 V AC (or about 120 V DC): can kill. Treat every lighting supply of 100 V or more as deadly.

Alternating current is more dangerous than direct current of the same voltage, because it clamps the muscles and disturbs the heart more easily.

Why wires get hot

Every wire has resistance, and the current through it makes heat — four times as much heat for twice the current. A wire that is too thin for its current gets hot, its insulation chars, and wood or straw nearby can catch fire. It also wastes voltage: a long thin wire to a distant lamp leaves the lamp dim.

The two kinds of fault

  • Overload: too many lamps or motors on one wire. The current is too high, but slowly; the wire heats over minutes or hours.
  • Short circuit: the two wires of a circuit touch, or a wire touches earthed metal. The current is enormous, instantly. Wires can melt, spray molten copper and start fires in seconds.

A fuse handles both: it is a deliberately weak link, a short piece of thin wire that melts and breaks the circuit before the main wiring gets dangerously hot.

Live, neutral and earth

Connect one wire of the generator firmly to the earth, right at the generator. That wire is now called the neutral: it stays at about the same voltage as the ground, so touching it alone does nothing. The other wire is the live: touching it while standing on the ground puts the full supply voltage across your body. Once you know which is which, you can put every fuse and every switch in the live wire, so that a blown fuse or an open switch leaves the lamp, motor or socket beyond it truly dead.

A third wire, the earth wire (protective conductor), runs alongside every circuit to the metal case of every machine and back to that same earthing point at the generator. If the live wire ever touches the case, the current rushes along the earth wire back to the generator — a short circuit — and the fuse blows at once. Without it, the case simply sits at the supply voltage, waiting for someone to touch it.

Generator Fuse board double-polemain switch mainfuse Neutral earthedat the generator Earth rod or platein damp ground LIVE NEUTRAL EARTH WIRE Lampfuse and switchin the live wire Socketbig earth pin Motormetal caseearthed A fault from live to the case flows back alongthe earth wire and blows the fuse at once.
Fig. 1 A small installation. One wire of the generator is earthed at the source and becomes the neutral. The live wire goes through the main switch and main fuse to a board of branch fuses, then to each circuit's switches. A separate earth wire runs to the metal case of the motor and the earth pin of the socket.

What you need

Item Notes
Insulated copper wire of the right thickness (table below) Copper Wire; varnished cotton or rubber covering (Rubber)
Flexible cord for lamps and portable tools Many fine strands twisted together, each 0.2–0.3 mm
Insulators: knobs, cleats, tubes Glazed porcelain or stoneware (Stoneware and Porcelain), glass
Fuse wire Thin copper or tin–lead wire (Tin and Pewter, Lead)
Fuse holders, switch and board bases Slate, marble or glazed fired clay (Quarrying and Cutting Stone); hardwood only for low voltage
Brass for terminals, switch blades, plug pins Zinc and Brass
Earth electrode Copper plate 60 × 60 cm, or 2–3 m of copper or iron rod or pipe
Solder, varnish, cotton tape Soldering and Brazing, Copper Wire
Test lamp A lamp for your supply voltage on two insulated leads

Where to find it

Everything is made in other chapters. The most important home-made parts are the non-burning bases. Slate splits into flat sheets that do not burn and insulate well when dry; marble cuts and drills easily; porcelain (Stoneware and Porcelain) can be moulded into knobs, tubes, fuse holders and switch bases. Wood is acceptable for low-voltage (under 25 V) work and for dry, low-current fittings, but never for fuse holders or main switches.

Step 1: Choose the wire

Thick enough to stay cool

For copper wire with home-made covering (varnished cotton or wax, which cannot stand much heat), in open air:

Copper cross-section Diameter Safe current Typical use
0.75 mm² 1.0 mm 5 A Lamp cords
1.5 mm² 1.4 mm 10 A Lighting circuits
2.5 mm² 1.8 mm 15 A Sockets, small motors
4 mm² 2.3 mm 20 A Workshop circuits
6 mm² 2.8 mm 30 A Main feed from the generator
10 mm² 3.6 mm 45 A Large mains

Wire bundled together, buried in walls, or in hot places must be thicker. Iron wire of the same thickness heats much faster and wastes six times as much voltage: give it no more than a third of these currents.

Thick enough not to waste voltage

For a long run, check the voltage lost along the way. For a copper circuit (out and back), the voltage lost is about:

volts lost ≈ 0.035 × length of run in metres × current in amps ÷ cross-section in mm²

Keep it under 5% of your supply (5 V on a 100 V supply). Example: a workshop 40 m from the generator draws 8 A at 100 V. Required cross-section = 0.035 × 40 × 8 ÷ 5 = 2.2 mm², so use 2.5 mm². For runs of hundreds of metres, raise the voltage with a The Transformer instead of using impossibly thick wire.

Step 2: Run the wires

Open wiring on porcelain knobs 6–8 cm apart knob every 1–1.5 m knobs hold wires 2–3 cm off the walltube A sound joint 1. Twist tight, 5 turns each way 2. Solder right through 3. Two layers of varnished tape Fuse in a covered holder porcelain or slate cover fuse wire brass terminal porcelain or slate base live wire in and out Knife switch hinge brass blade insulated handle jaws spring snaps it open slate base
Fig. 2 Wiring details. Open wiring on porcelain knobs, wires kept apart and off the wall; porcelain tubes through walls. A joint is twisted tight, soldered and taped. Fuses sit in covered porcelain or slate holders. The knife switch has a slate base and a spring that snaps it open.

Open wiring on knobs is the simplest safe method without good rubber insulation, and lit millions of houses from the 1880s to the 1930s:

  1. Fix porcelain knobs or cleats to walls and ceilings every 1–1.5 m, with a nail or screw through the centre.
  2. Tie each wire to its knobs with soft wire or waxed cord, keeping the two wires at least 6–8 cm apart and 2–3 cm away from the wall or beam.
  3. Where a wire passes through a wall, floor or beam, pass it through a porcelain or glazed clay tube, one tube per wire.
  4. Keep wiring away from straw, thatch, hay, damp corners, chimneys and stove pipes. Run it high, out of reach of children and animals.
  5. In damp rooms, outdoors and in barns, use only well-varnished or rubber-covered wire on glass or porcelain insulators, or put the wire in iron or fired clay pipe (Tiles and Clay Pipes).
  6. Between buildings, run wires overhead on poles and insulators as for the The Telegraph, at least 5 m above the ground, or underground in pipes filled with hot pitch.

Joints are where most electrical fires start, because a loose joint has resistance and gets hot:

  1. Scrape the ends bright and clean for 5 cm.
  2. Cross them and wrap each end tightly round the other wire at least 5 times (the "Western Union" splice).
  3. Solder it (Soldering and Brazing) — run solder right through the twists.
  4. Wrap it in varnished cotton tape, overlapping by half, two layers thick, past the bare copper on both sides.

Or make joints with brass screw terminals inside a covered porcelain or clay junction box (Insulators, Cables and Electrical Fittings shows how to make boxes, lamp holders and ceiling roses). Never leave a joint just twisted.

Step 3: Fuses and breakers

The fuse

  1. Holder: a base of porcelain, slate or glazed clay with two brass terminals 3–5 cm apart, and a cover of the same material, so that the flash and molten metal when it blows cannot reach anything that burns.
  2. Fuse wire is stretched between the terminals. For tinned copper wire, approximately:
Circuit rating Copper fuse wire diameter
5 A 0.20 mm
10 A 0.35 mm
15 A 0.50 mm
20 A 0.60 mm
30 A 0.85 mm

A fuse of this kind carries its rating indefinitely and melts within a minute or so at about twice it. Tin–lead or lead wire melts at a lower temperature and must be thicker for the same rating. 3. Calibrate your own wire, because home-drawn wire varies. Make a test load — a bank of lamps, or a coil of iron wire in a bucket of water — and an ammeter (Measuring Electricity). Find the thinnest wire that carries the rated current for an hour without melting, but melts within a minute at double it. Keep a labelled card of each size beside the fuse board. 4. The fuse must be smaller than the wire. A 15 A fuse protects 2.5 mm² wire; it does not protect a 0.75 mm² lamp cord, which needs its own 5 A fuse. 5. One fuse per circuit, plus a main fuse, all in the live wire.

Warning Never replace a fuse with thicker wire, a nail or a coin "because it keeps blowing". A fuse that keeps blowing is telling you about an overload or a fault. Find it. Bridging the fuse turns the house wiring into the fuse.

The circuit breaker

A breaker is a switch that throws itself open on too much current and can be reset by hand. A simple one from The Electromagnet parts:

  1. A knife switch whose blade is pulled open by a strong spring, but held closed by a latch.
  2. A coil of a few turns of thick wire, carrying the circuit's full current, with an iron armature above it.
  3. When the current rises past the set value, the coil pulls the armature down; the armature knocks the latch free; the spring snaps the switch open.
  4. Set the trip point by adjusting the armature's gap and spring, using the same test load as for fuses — trip at about 1.5–2 times the rating.

A magnetic breaker acts fast on short circuits but ignores slow overloads, so keep fuses as well.

Step 4: Earthing

  1. Earth the neutral at the source. Bury a copper plate 60 × 60 cm upright in permanently damp ground 1.5–2 m deep, or drive 2–3 m of copper or iron rod or pipe, near the generator. Pack it round with crushed charcoal or coke and water it well. Connect one generator terminal to it with copper wire at least as thick as the main wires. This is now the neutral.
  2. Run an earth wire — copper, at least 2.5 mm² — alongside every circuit, to the metal case of every motor, pump, lamp fitting and tool, and to the earth pin of every socket. Connect it back to the neutral at the generator's earthing point.
  3. Earth metal pipes, tanks and sinks near wiring to the same earth wire.
  4. Mark the wires. Choose a system and keep it everywhere: for example red thread wound on the live wire at every joint and terminal, black on the neutral, green on the earth. Write the system in the logbook kept beside the fuse board.

Note Why not just drive a rod into the ground by each machine? Soil is a poor conductor. Two earth rods might have 20–50 Ω between them. A live wire touching a case on 100 V then pushes only 2–5 A through the ground — not enough to blow a 10 A fuse — and leaves the case at a deadly 50 V or more. Only a wire back to the generator makes the fault a true short circuit that blows the fuse. Extra earth rods at each building help, but never replace the earth wire.

Step 5: Switches and sockets

  • Knife switch (the easiest to make): a brass blade pivoted at one end, closing into a pair of springy brass jaws, on a slate or porcelain base, with an insulated handle of wood or horn. A spring on the blade that snaps it open quickly stops a long arc forming. Enclose it in a box with only the handle outside. On DC, arcs are much harder to break: make the gap wider (2–3 cm) and the snap faster.
  • Main switch: double-pole — it opens both live and neutral at once — so the whole installation can be made dead before work.
  • Lamp switches go in the live wire, never in the neutral.
  • Sockets: two brass sockets for the plug pins, sunk at least 5 mm below the face of a porcelain, slate or hardwood block, so fingers cannot touch them; and a third, larger socket for the earth pin. Make the earth pin of the plug longer than the others, so it connects first and disconnects last. Make the live and neutral pins different sizes so the plug fits only one way round.
  • Plugs: a hardwood, porcelain or moulded (Early Plastics) body with brass pins 4–5 mm thick, 2 cm apart. A cord grip inside clamps the cord's covering, so a pull on the cord never pulls on the terminals.
  • Lamp cords: flexible cord, never solid wire, which breaks with bending.

Step 6: Work safely

  1. Switch off and isolate: open the main switch, take out the fuse and keep it in your pocket, and hang a sign on the board: "MEN AT WORK — DO NOT SWITCH ON".
  2. Test that it is dead with a test lamp. Test the test lamp on a circuit you know is live before and after, so a broken lamp does not tell you a lie.
  3. Use one hand where you can, keeping the other in your pocket, so current cannot cross your chest.
  4. Stand on dry wood or a dry mat, in dry boots. Never work on live gear with wet hands or in rain.
  5. Never work alone on anything over 50 V. The second person must know where the main switch is and how to give first aid.
  6. Inspect wiring every year: look for scorched insulation, warm joints (feel them with the back of the hand under load), loose knobs, chewed wires (rats love wax and rubber), and cracked porcelain.

How to tell it worked

  • Polarity: with a test lamp between each socket's live terminal and the earth wire, the lamp lights; between neutral and earth, it does not.
  • Earth test: with the supply on and a fuse in, briefly connect the live terminal to an earthed case through a short thick wire: the fuse must blow at once. Do this only with a correct fuse in place, using insulated tools, standing well back.
  • Warmth: after an hour at full load, wires and joints should feel no warmer than the room; fuse covers barely warm.
  • Insulation: with the supply off, a battery and galvanometer (The Electromagnet) between each wire and earth should show no current.

Note Troubleshooting. Fuse blows the moment you switch on → short circuit: wires touching, or a live wire touching earthed metal. Divide the circuit into halves and test each. Fuse blows after some minutes → overload. Spread the load over more circuits. Lamps dim when a motor starts → wires too thin or too long; see the voltage-drop rule. A tingle from a metal case → a leaking or broken earth wire. Switch off at once; find and fix it before using that machine again. Joint or switch warm or discoloured → loose or dirty contact. Remake it. Breaker trips for no reason → set too sensitive; or a motor's starting current. Raise the setting a little, never above the wire's safe current.

Dangers

Danger Electric shock kills. Any supply above about 50 V AC can stop the heart, and wet skin makes even lower voltages dangerous. Switch off, isolate, and test before touching. Never trust a switch alone — pull the fuse.

Danger Overhead lines. Never touch, climb near, or throw anything at a power line. A high-voltage line (over 1,000 V) can jump to a ladder, a pole or a person who comes close, and a fallen one makes the ground around it live. Stay at least 18 m (about 20 paces) away from a fallen line until the power is off — further on wet ground. If your feet tingle, shuffle away with tiny steps, feet together.

  • Fire. Overloaded wires, bad joints and arcing switches start fires inside walls and roofs. Keep wiring away from thatch, hay and straw, fuse every circuit, and inspect it.
  • Burns from arcs. A short circuit at the main fuse or generator can flash molten copper. Wear eye protection when working near live main conductors; never bridge them with tools.
  • Generators and transformers: see The Generator and The Transformer.

First aid for electric shock

  1. Do not touch the person while they are still in contact with the current. You will be caught too.
  2. Cut the power: open the switch, pull the fuse or plug. If you cannot, and the supply is ordinary low voltage (under 1,000 V), stand on dry wood, dry cloth or a dry board, and push or pull them free with something dry that does not conduct — a dry wooden pole or broom handle, a rope looped round an arm or foot, a dry leather belt. Never use anything wet or metal.
  3. For high-voltage lines, stay at least 18 m away and do not approach until the power is confirmed off.
  4. Check breathing. If they are not breathing normally, start CPR at once — 30 pushes and 2 breaths (Emergencies). A shock can stop breathing while the heart still beats, and rescue breaths alone may save them; if the heart is quivering, CPR keeps blood flowing to the brain while you keep trying. Do not give up early.
  5. If breathing, put them in the recovery position and watch them closely.
  6. Burns: electricity burns where it enters and leaves — often a hand and a foot. Cool them under clean, cool running water for 20 minutes and cover loosely with a clean cloth (Wound Care and Antiseptics). The damage inside is usually far worse than the small marks outside.
  7. Watch for 24 hours. Anyone who had a shock across the chest, was knocked out, or has burns should rest and be watched closely for a day: heart rhythm problems can start hours later. Dark or reddish urine means muscle damage — give plenty to drink and seek the best help available.

What this unlocks

Safe wiring is what turns a generator into lighting for a whole village: The Light Bulbs in every house, The Electric Motors driving pumps and tools, Electrolysis and Electroplating works, and eventually the Power Lines and Distribution that links many generators. The same habits protect the operators of The Telegraph, The Telephone and Radio equipment.

Going further: the residual-current device (earth-leakage breaker) compares the current going out on the live wire with the current coming back on the neutral, by passing both wires through a small iron ring with a sensing coil — a The Transformer with a sensitive relay. If even 30 mA is leaking away through a person, the currents differ, and it trips in a fraction of a second. It is the single best protection against fatal shocks, and is worth building once you can make sensitive relays; Motor Starters, Contactors and Protection shows how.

How it was first done

The first electric lighting installations of the late 1870s and early 1880s were wired with bare or cotton-covered wire, and fires followed. Thomas Edison's lighting systems of 1880–82 included lead "safety wires" — fuses — in small porcelain holders, one for each branch. In Britain the Society of Telegraph Engineers and Electricians issued its first rules for electric lighting installations in 1882; they grew into the national wiring regulations. In the United States, fire insurers pushed for common rules, and the first National Electrical Code was published in 1897. "Knob-and-tube" open wiring on porcelain was the standard in American houses from the 1880s into the 1930s.

The miniature circuit breaker was developed in Germany in the 1920s by Hugo Stotz's company, and grounding of the neutral and of metal cases became standard practice in the first half of the 20th century. Residual-current devices that trip at about 30 mA spread from the 1960s and 1970s, and are now required in homes in much of the world.

Source: content/entries/electricity/wiring-and-safety.md