Part 6 · Building

Clean Rooms

A clean room holds a thousand to a million times less dust than ordinary air. It is needed to make microchips, sterile injections and vaccines, precision bearings and optics, and to operate on joints without infection. This chapter covers counting particles and the classes of cleanliness, the HEPA filter and how to make and test one, the laminar flow bench, the room with its filtered ceiling, pressure steps and smooth walls, the changing rooms, airlocks, pass boxes and air showers that guard it, and the gowns and habits of the people inside, who are its main source of dirt.

Difficulty
●●●●●
Time
A week to build and test a clean bench once filter paper exists; two to three months to build and commission a small clean room
Steps from zero
43 prerequisites →

You need first

Ventilation and Air ConditioningGlass Fibre and Glass Wool

This unlocks

Making Microchips
The full path from nothing — 43 steps before this one
  1. Fire
  2. Cordage and Rope
  3. Stone Tools
  4. Finding and Preparing Clay
  5. Finding and Identifying Ores
  6. Hunting and Trapping
  7. Basic Woodworking
  8. The Kiln
  9. Charcoal
  10. Pottery
  11. Hides and Leather
  12. Bricks
  13. Salt
  14. Lime
  15. Fermentation
  16. Lye and Potash
  17. The Wheel and Axle
  18. Firebrick and Refractories
  19. Glass
  20. Bellows
  21. Gears
  22. The Lathe
  23. Glass Fibre and Glass Wool
  24. Iron (the Bloomery)
  25. Copper Smelting
  26. Laboratory Glassware
  27. The Waterwheel
  28. Pumps
  29. The Blast Furnace and Cast Iron
  30. Bronze
  31. Blacksmithing
  32. The Battery
  33. Steel
  34. Chimneys, Stoves and Heating
  35. Bearings and Lubrication
  36. The Steam Engine
  37. Electrolysis
  38. Hydrogen, Oxygen and Gases
  39. Centrifugal Pumps and Fans
  40. Machine Tools
  41. Ammonia
  42. Ice and Refrigeration
  43. Ventilation and Air Conditioning
  44. Clean Rooms

Do them roughly in this order. See it on the tech tree →

Why it matters

Ordinary air is full of dust: in a town, some 35 million particles larger than half a micrometre in every cubic metre. Most are too small to see. They do no harm to ordinary work, but some work they ruin:

  • Microchips. One speck on a mask or wafer kills the circuit under it (Making Microchips). Chip making is impossible without clean air.
  • Medicines. Injections, eye drops, Intravenous Fluids and vaccines that cannot be sterilised after filling must be filled where no germ can fall in (Making Medicines, Vaccination). Germs ride on skin flakes and dust.
  • Surgery. After a hip or knee is replaced, a few bacteria settling into the wound from the air can cause a deep infection that destroys the joint. Ultra-clean air over the table cut such infections from several percent to under one percent (Basic Surgery).
  • Precision work. Gyroscopes (Gyroscopes and Inertial Guidance), lens coatings (Vacuum Coating and Thin Films), film and spacecraft all fail from dust.

A clean room holds a thousand to a million times fewer particles than outside air. It is mostly a matter of air handling (Ventilation and Air Conditioning) and discipline.

How it works

Where the dirt comes from

Dust comes in with the air, on things, and is made inside, above all by people, whose skin sheds and clothes rub off fibres. A person sitting still gives off about 100,000 particles of 0.3 µm and larger every minute; walking, about 5 million; walking fast or swinging the arms, 10 million or more. Skin flakes of 10–20 µm carry bacteria. Talking, coughing and sneezing spray droplets.

So a clean room works on three rules:

  1. Keep dirt out: supply only filtered air, keep the room at a higher pressure than its surroundings so air leaks out and never in, and bring in people and things only through airlocks.
  2. Do not make dirt inside: smooth, hard, non-shedding surfaces; gowns that hold the body's dust in; slow, careful movement; nothing that sheds, such as wood, paper, cardboard or cotton.
  3. Sweep it away fast: a strong flow of clean air that carries off whatever is made before it can land on the work.

Classes

Cleanliness is measured by counting particles larger than a given size in a cubic metre of air. The international classes (ISO) go up by ten times at each step:

Class Particles ≥ 0.5 µm per m³ Old US class (per cubic foot) Typical use
ISO 3 35 1 Modern chip lithography
ISO 4 352 10 Chip making
ISO 5 3,520 100 Inside a clean bench; sterile filling; chips of the 1970s
ISO 6 35,200 1,000 Precision assembly
ISO 7 352,000 10,000 Room around a sterile filling bench; operating theatres
ISO 8 3,520,000 100,000 Changing rooms, preparation rooms
ISO 9 35,200,000 Ordinary room air

Medicine makers also count live germs: an open dish of nutrient jelly (a settle plate, Culturing Microbes) left 4 hours near the work should grow no colonies at all in the zone where sterile products are open to the air, no more than 5 in the room around it, and no more than 50–100 in the preparation rooms.

The HEPA filter

A HEPA filter (high-efficiency particulate air) stops at least 99.97% of particles 0.3 µm across, and even more of larger and smaller ones. It is a deep-pleated paper of very fine glass fibres, 0.5–2 µm thick, much thinner than a hair. It is not a sieve: the gaps between fibres are far bigger than the particles. Particles are caught three ways:

  • Big ones cannot follow the air as it swerves round a fibre, and hit it.
  • Middle-sized ones follow the air but brush against a fibre in passing, and stick.
  • Tiny ones jitter about, knocked by air molecules, and wander into a fibre.

Particles of 0.1–0.3 µm are hardest to catch, too big to wander and too small to hit, so filters are rated there. Once a particle touches a fibre it sticks for good.

Air flow

  • Mixing flow, for ISO 6–8: filtered air enters through ceiling filters, mixes with the room air and dilutes the dust, and leaves through grilles low on the walls. It needs 20–60 air changes an hour (the room's whole volume of air replaced 20–60 times).
  • Unidirectional flow (often called laminar flow), for ISO 5 and cleaner: the whole ceiling (or wall) is filters, and air moves in straight, parallel lines at 0.3–0.5 m/s, about walking pace, sweeping straight down past the work to a perforated floor or low wall returns. Dust made at any point is swept downstream at once and never crosses the work, provided nothing upstream of the work makes dirt.

The air volumes are huge. Most of it is recirculated through the filters again; only 5–10% is fresh outside air, enough for breathing and to keep the room pressurised. The plant holds the room at about 20–22 °C and 40–50% relative humidity: drier air makes static, damper air grows mould.

What you need

Item Use See
Glass microfibre, 0.5–2 µm HEPA filter paper Glass Fibre and Glass Wool, Paper
Aluminium foil or sheet, plywood, sealant or wax Filter frames and pleat spacers Aluminium, Plywood, Veneer and Boards
Centrifugal fans, motors, speed control Clean benches and rooms Centrifugal Pumps and Fans, Motor Starters, Contactors and Protection
Pre-filters, air handling plant Protecting the HEPA filters Ventilation and Air Conditioning
Smooth hard finishes: enamel paint, steel or aluminium sheet, sealed plaster, epoxy, welded vinyl Walls, ceilings, floors Pigments, Paints and Varnish, Petrochemicals and Modern Plastics
Tightly woven synthetic cloth Gowns Rayon and Nylon, Sewing, Needles and Thread
Inclined manometer, anemometer, smoke source, strong lamp Testing Pressure and Vacuum Gauges, Rain Gauges, Anemometers and Weather Stations

Making a HEPA filter

  1. The paper. Make glass microfibre by blowing or spinning molten glass into fibres as fine as you can, 0.5–2 µm (Glass Fibre and Glass Wool). Beat it into water with a few percent of longer, thicker glass fibres for strength, and form it into a sheet on a fine screen like hand-made Paper, about 0.4–0.5 mm thick. A very little binder (a starch or resin, 3–5%) holds it together; too much clogs the pores. Dry it flat.
  2. Test the paper. Clamp a disc in a holder, blow smoky air through it at 2–3 cm/s, and look at the air coming out in a strong beam of light in a dark room (below). It should be completely dark. The pressure drop across the paper should be roughly 120–180 Pa (12–18 mm of water) at that speed, or about 250–300 Pa at 5 cm/s; far more means the paper is too dense, far less that it is too open.
  3. Pleat it. Fold the paper back and forth into pleats 15–30 cm deep, held apart by corrugated aluminium separators or by beads of glue along the pleats. Pleating puts 10–20 m² of paper into a frame 60 cm square, so even when air leaves the face of the filter at 0.45 m/s or faster, it passes through the paper itself slowly, at only 1–3 cm/s.
  4. The frame. A box of plywood or aluminium. Seal the pleat pack into it on all four sides with a thick bead of sealant, molten wax or resin (Resins: Phenolic, Polyester and Epoxy): air that goes round the paper is not filtered. Glue a soft rubber or felt gasket on the face that seals against the housing.
  5. Mount it in a housing that clamps it hard and evenly against the gasket, and put a pre-filter of cheaper media upstream to catch coarse dust and lengthen its life.

A standard filter 61 × 61 cm and 29 cm deep passes about half to one cubic metre of air a second with a starting pressure loss of 150–250 Pa. Change it when the loss doubles, or when a leak test fails.

Leak test. Fill the air upstream with fine smoke: oil heated until it smokes, or a smouldering cotton wick. In a darkened room, shine a narrow, strong beam of light just downstream of the filter face, and sweep a thin probe tube or your eye slowly over every part of the face and every edge of the frame. Clean air is black in the beam; a leak shows as a bright, glittering stream. Seal pinholes with a dab of silicone or wax, and edge leaks by reseating the gasket. Factories measure the smoke with a light-scattering meter and allow no spot where more than 0.01% of the upstream smoke gets through.

The laminar flow bench

A laminar flow bench (clean bench) gives an ISO 5 working space in an ordinary room. It is the first piece of clean equipment to build, and for a small laboratory, pharmacy or chip workshop it may be all you need. Making Microchips gives the basic dimensions; here is the detail.

pre-filter: room air in fan 300–400 Pa sealed plenum behind HEPA filter: whole back wall work surface One pleat, enlarged glass microfibre paper, 0.4–0.5 mm thick; air crosses it at 2–3 cm/s
Fig. 1 A horizontal laminar flow bench in section. Room air is drawn through a pre-filter at the top by a centrifugal fan into a sealed plenum behind the HEPA filter, which forms the whole back wall of the work space. Clean air leaves the filter face at 0.45 m/s in straight lines across the work surface and out at the front, past the worker's hands. Inset: one pleat of the HEPA filter, glass microfibre paper held apart by a corrugated aluminium separator.
  1. Size: work space about 120 cm wide, 60 cm deep and 70 cm high, open at the front.
  2. Filter: a HEPA filter forming the whole back wall, here about 1.2 × 0.6 m.
  3. Air flow: 0.45 m/s × 0.72 m² = 0.32 m³ a second, about 1,200 m³ an hour.
  4. Fan: a centrifugal fan (Centrifugal Pumps and Fans) drawing room air through a pre-filter in the top or bottom of the cabinet, and pushing it into a sealed plenum (an air chamber) behind the HEPA filter. It must give about 300–400 Pa at full flow, so it can still push enough air when the filter is half clogged. Fit a speed control (Motor Starters, Contactors and Protection), or a damper, to set the velocity. Mount it on rubber so it does not shake the bench.
  5. Evening the flow: a perforated metal screen over the filter face, or a sheet of fine cloth, evens out the speed.
  6. Body: steel or aluminium sheet, enamelled, smooth inside; work surface of stainless steel or glass.

Testing. Measure the air speed with a small vane anemometer (Rain Gauges, Anemometers and Weather Stations) at nine points across the face: every reading should be within ±20% of 0.45 m/s. A thin thread or a wisp of smoke held anywhere in the work space should stream straight out towards the front, never curl back.

Using it.

  • Switch it on 15 minutes before work. Wipe the surfaces with 70% alcohol.
  • Keep everything you work on between the filter and your hands, never downstream of them. Nothing large between the filter and the critical work; it casts an "air shadow" of eddies.
  • Work at least 15 cm inside the front edge. Move slowly. Do not talk or cough towards the work.

Warning A horizontal clean bench blows across the work straight into your face. It protects the work, not you. Never use it for disease germs, cultures of unknown organisms, or poisonous or drug powders. For those use a biological safety cabinet: air flows down onto the work from a filter above, is drawn in at the front opening and away from the worker, and is blown out through a second HEPA filter (The Medical Laboratory).

The clean room

The room

filtered air from the plant corridor 0 Pa changing room +10 Pa airlock +20 Pa clean room +30 Pa fan filter units step-over bench sticky mat pass box returns low on the walls air leaks out toward dirtier side
Fig. 2 A small clean room suite in section. Air from the plant is blown through fan filter units covering the ceiling of the clean room, flows down past the work and returns through low grilles in the walls. People pass from the corridor through a changing room with a step-over bench and an airlock with interlocked doors; materials pass through a pass box. Each room is held 10–15 pascals above the one outside it, so air always leaks outward toward the dirtier side.
  • Walls and ceiling: smooth, hard, sealed and washable. Steel or aluminium panels, or plaster sealed with hard enamel or epoxy paint. Every joint sealed.
  • Corners: coved, curved with a radius of 3–5 cm where walls meet floor and ceiling, so dust cannot lodge and a mop reaches everywhere.
  • Floor: seamless: welded vinyl sheet, epoxy, or polished terrazzo (Laying Tiles and Mosaics).
  • No ledges: windows glazed flush on the clean side, lights sealed flush into the ceiling, pipes and wires run outside the room and enter through sealed holes.
  • Doors: few, close-fitting, self-closing, with windows so people do not open them blind.
  • Ceiling: filters set into a sealed grid. Ready-made fan filter units make this simple: each is a box about 120 × 60 cm with a small fan on top and a HEPA filter below, dropped into the ceiling grid. Cover 15–25% of the ceiling for an ISO 7 room, and 60–100% for ISO 5.
  • Returns: grilles low on the walls, spread round the room, so the air moves downward everywhere.

Example: a small ISO 7 room 6 × 4 m and 3 m high, 72 m³, at 40 air changes an hour needs about 2,900 m³ of filtered air an hour: three fan filter units at 0.45 m/s (each passes about 1,150 m³ an hour), or four to six run more slowly, which spreads the flow more evenly. To make the same room ISO 5 with a fully filtered ceiling (24 m² at 0.45 m/s) takes about 39,000 m³ an hour, thirteen times as much. Make only the small zone where the work is open to the air ultra-clean, with clean benches or a filtered canopy over it, and keep the room around it at ISO 7.

Pressure. Hold each cleaner room 10–15 Pa above the next dirtier one: clean room above airlock, airlock above changing room, changing room above corridor. Read the steps on inclined manometers (Pressure and Vacuum Gauges) mounted outside each door, and check them every shift. A strip of tissue at a door gap should lean outward from the clean side. Rooms handling germs or poisonous powders reverse this: they are held below their surroundings, with a clean-air lock in between.

Airlocks, pass boxes and air showers

  • Changing room: entered from the corridor, with sticky mats on the floor (tacky sheets that lift dust off shoe soles) and a step-over bench across the room: the dirty side for street shoes and outer clothes, the clean side for gowns. You sit on the bench, swing one leg over, put on an overshoe, set that foot down on the clean side, then do the other.
  • Airlock: a small room between changing room and clean room, with two doors interlocked so they can never both be open: a latch or electric lock on each door that is released only when the other is shut (Locks and Keys, Insulators, Cables and Electrical Fittings).
  • Pass box: a cabinet through the wall, about 50–60 cm each way, with an interlocked door on each side and a smooth steel lining, for passing materials without people. Wipe everything with alcohol as it goes in. Some have their own HEPA fan.
  • Air shower: a booth about 1 × 1 × 2.1 m between airlock and clean room. Nozzles in the walls and ceiling blow filtered air at 20–25 m/s at the gowned person for 15–30 seconds while they turn round slowly with arms raised; the air is drawn out at the floor, through a pre-filter and a HEPA filter, and blown round again. It knocks loose dust off the gown and reminds people where they are going, but it is no substitute for good gowns and habits.

The cleanroom gown

The gown is not to protect the wearer. It is a bag to hold the wearer's dust in.

hood tucks into collar goggles mask one-piece coverall polyester or nylon, zip under a flap, no pockets knitted cuffs gloves over cuffs boots over the legs Put on top to bottom: hood, mask, coverall, boots, goggles, gloves. fan and HEPA filter floor grille: air drawn out and filtered again nozzles, 20–25 m/s turn slowly, 15–30 s
Fig. 3 The gowned worker and the air shower. The hood covers the head and neck and tucks into the coverall; a mask covers nose and mouth; goggles if needed. The one-piece coverall closes with a zip under a flap, with knitted cuffs at wrists and ankles; boots come up over the legs of the coverall; gloves pull up over the cuffs. Right: the air shower, a booth with nozzles in its walls blowing filtered air at the turning worker, with doors at each end that cannot both open at once.

Cloth. It must shed nothing. Continuous-filament polyester or nylon (Rayon and Nylon), tightly woven so that the gaps are smaller than skin flakes, is the standard; a grid of fine carbon-loaded threads woven in every centimetre or so leaks away static. Before synthetic fibres, tightly woven silk is the best substitute (Silk). Cotton and wool shed lint and are wrong for anything cleaner than about ISO 8, though cotton theatre gowns served surgery for a century.

Making it.

  1. Coverall: one piece, loose enough to move in without strain, with a zip down the front under a covering flap. No pockets, no pleats, no belts, no buttons. Knitted cuffs of the same fibre at wrists and ankles close round the body (Knitting, Crochet and Netting).
  2. Hood: covers head, ears and neck, with a long skirt that tucks inside the coverall's collar, and a face opening fitting snugly round mask and goggles.
  3. Boots: knee-high, with a slip-resistant sole of rubber or plastic, fastened at the top over the coverall legs.
  4. Seams: every cut edge enclosed, bound or folded under and double-stitched, because a raw edge frays and sheds (Sewing, Needles and Thread). Use synthetic thread.
  5. Mask: several layers of fine woven synthetic cloth or filter fabric over nose and mouth. Gloves: rubber or synthetic (Rubber), pulled over the cuffs.
  6. Laundering: wash in filtered, deionised water (Water Softening and Ion Exchange) with little detergent, dry in filtered air, fold and seal in clean bags inside a clean area. Gowns go out for washing after each day or each entry; boots and hoods last longer.

Putting it on, top to bottom, so that nothing clean touches anything dirty: wash hands; overshoes across the step-over bench; hood; mask; coverall, without letting it touch the floor; boots; goggles; gloves, pulled over the cuffs; check yourself in a full-length mirror.

Habits. No cosmetics, food, chewing or smoking; no ordinary paper, pencils or cardboard. Move slowly; do not lean on walls. Only those who need to be inside go in; anyone with a cold or peeling sunburn stays out.

How to tell it worked

  • Particle count, without instruments: in a darkened room, shine a narrow, strong beam of light across the air you want to judge, and look along it against a black background. Ordinary room air glitters with countless specks. ISO 7 shows a few now and then. Inside a good clean bench, you should see nothing at all for minutes. Witness plates: leave clean black glass plates or microscope slides on the work surface for a day, then count specks on a measured area under a microscope (The Microscope); compare day by day.
  • Particle counter: a factory instrument draws a measured stream of air through a beam of light and counts the flashes as particles cross it, sorting them by size by the brightness of each flash. It needs Photocells and Sensors and counting electronics.
  • Germs: settle plates as above.
  • Pressure: each manometer reads its 10–15 Pa step; tissue leans outward at every door.
  • Flow: smoke released near the work rises from nothing and streams down or across, steadily, away from the work.
  • Results: chip yields rise, sterile batches pass their tests (Pharmacy: Tablets, Capsules, Ointments and Inhalers), joint infections fall.

Note Troubleshooting. Counts high near the work → filter leak (smoke test), gasket badly seated, people standing upstream of the work, too many people, fast movement. Counts rise after people enter → poor gowns (cotton, frayed seams, torn cuffs), wrong gowning order, cosmetics. Pressure steps fall → a door left open or ajar, a clogged supply filter, a fan belt slipping, a new hole through a wall. Smoke curls back towards the work → an obstruction or a hot lamp upstream, a cold draught from a door, air speed too low. Germs grow on settle plates → filter leak, poor wiping, contaminated gowns or gloves; clean with alcohol and a sporicidal disinfectant and retest.

Dangers

Danger Fire and fumes in a sealed room. A clean room is a sealed box of recirculating air. Smoke from a small fire, or a leak of solvent or poisonous gas from chip work (Making Microchips), spreads through the whole room in seconds. Fit smoke detectors in the return air, automatic shut-off of fans, clearly marked emergency exits that open outward without interlocks in an emergency, and gas detectors where gases are used (Fire Extinguishers and Alarms). Never block an escape route with equipment.

  • The wrong bench: a horizontal clean bench blows whatever is on it into the worker's face. Germs and drug powders belong in a safety cabinet.
  • Static: dry air and synthetic gowns make sparks that can ignite solvent vapour. Earth benches and metal fittings, and keep humidity above 35–40%.
  • Alcohol for wiping is flammable; use small amounts, never near hot plates or flames.
  • Disinfectants: rooms are sometimes fumigated with formaldehyde or hydrogen peroxide vapour (Methanol and Formaldehyde, Hydrogen Peroxide and Oxygen Bleach); no one may enter until it is cleared.
  • Heat and fatigue: a full gown is hot; allow breaks and keep the room cool.
  • Ultraviolet lamps fitted to kill germs on surfaces burn the eyes and skin. Switch them off before anyone enters.

What this unlocks

Clean rooms make possible the microchip industry and everything after it (Integrated Circuits, Microprocessors and Personal Computers), sterile manufacture of injections, eye drops and vaccines (Pharmacy: Tablets, Capsules, Ointments and Inhalers), joint replacement surgery (Crutches, Prosthetics and Rehabilitation), satellites (Spaceflight and Spacecraft), precision bearings and gyroscopes, coated optics and lasers (Lasers), and the ultra-pure water and chemicals those industries need (Water Softening and Ion Exchange, Membranes, Reverse Osmosis and Desalination).

How it was first done

Surgeons have fought airborne germs since Joseph Lister sprayed carbolic acid in his operating theatre in the 1860s. The HEPA filter was developed in the 1940s in the United States atomic bomb project, to catch radioactive dust. In 1960–62 the physicist Willis Whitfield at the Sandia laboratories in New Mexico designed the first laminar flow clean room, with filtered air sweeping steadily across the room, and it was hundreds of times cleaner than anything before. Within a few years clean rooms spread through the space and electronics industries; the US government published its Federal Standard 209 of cleanliness classes in 1963, replaced by the international ISO 14644 in 1999. In England the surgeon John Charnley, working with the engineer Hugh Howorth, built an enclosure of clean, downward-flowing air over the operating table for hip replacements in the 1960s, and with gowns that drew away the surgeons' own breath and dust he cut deep infections dramatically.