Part 6 · Building
Ventilation and Air Conditioning
How to move fresh air through rooms, mines, wards and workshops on purpose — by the stack effect and the wind, then with fans and ducts — how to catch dust and fumes at the machine before anyone breathes them, how to cool dry-country rooms with wet pads and a fan, and how an air conditioning plant with chilled water, coils and filters cools, dries and cleans the air of a hospital or a factory.
- Difficulty
- ●●●●●
- Time
- A day to cut vents and fit a windcatcher; a week or two to build a fan, ducts and a cyclone; months to build and balance an air conditioning plant
- Steps from zero
- 41 prerequisites →
This unlocks
Clean RoomsThe full path from nothing — 41 steps before this one
- Fire
- Cordage and Rope
- Stone Tools
- Finding and Preparing Clay
- Finding and Identifying Ores
- Hunting and Trapping
- Basic Woodworking
- The Kiln
- Charcoal
- Pottery
- Hides and Leather
- Bricks
- Salt
- Lime
- Fermentation
- Lye and Potash
- The Wheel and Axle
- Firebrick and Refractories
- Glass
- Bellows
- Gears
- The Lathe
- Iron (the Bloomery)
- Copper Smelting
- Laboratory Glassware
- The Waterwheel
- Pumps
- The Blast Furnace and Cast Iron
- Bronze
- Blacksmithing
- The Battery
- Steel
- Chimneys, Stoves and Heating
- Bearings and Lubrication
- The Steam Engine
- Electrolysis
- Hydrogen, Oxygen and Gases
- Centrifugal Pumps and Fans
- Machine Tools
- Ammonia
- Ice and Refrigeration
- Ventilation and Air Conditioning
Do them roughly in this order. See it on the tech tree →
Why it matters
Smoke from indoor fires, carbon monoxide from stoves, dust from grinding and sawing, fumes from forges and acids, germs coughed into a crowded ward, the gases of a mine — every one is beaten the same way: bring clean air in, take dirty air out, and make it flow the way you want.
Ventilation is cheap and it saves lives: a cross-ventilated ward spreads tuberculosis far less than a closed one, and a grinding wheel with a hood does not fill a man's lungs with stone. Once you have Ice and Refrigeration, the same fans and ducts can carry cooled, dried and filtered air: an operating theatre that stays clean and cool, a store where medicines keep, a house where people can sleep in a humid summer.
How it works
Warm air rises: the stack effect
Warm air is lighter than cool air. A column of warm air inside a building pushes up and out through openings near the top and pulls cool air in near the bottom: the stack effect, the same thing that makes a chimney draw (Chimneys, Stoves and Heating). The push is small but free:
pressure (Pa) ≈ 0.04 × height between the low and high openings (m) × temperature difference (°C)
A room with openings 3 m apart in height and 10 °C warmer than outside makes about 1.2 Pa — about a tenth of a millimetre of water. With equal-sized low and high openings, each of area A (m²), the flow is roughly
air flow (m³ per second) ≈ 0.1 × A × √(height × temperature difference)
So two vents of 50 × 50 cm, 4 m apart in height, 10 °C warmer inside, move about 0.16 m³/s — nearly 600 m³ an hour.
Wind: pressure and suction
Wind presses on the side of a building it hits and sucks on the far side and on the roof. Openings on both sides give cross-ventilation, which moves far more air than the stack effect whenever there is any breeze. It works for rooms up to about 5 times the ceiling height deep; a room with windows on one side only is ventilated well only about 2½ times the ceiling height in from the window.
How much air?
Measure ventilation as air changes per hour — how many times the room's whole volume is replaced in an hour — or as litres per second per person.
| Place | Fresh air needed |
|---|---|
| Any occupied room, at the very least | 8–10 L/s per person (30–36 m³/h) |
| Kitchen while cooking | 10–15 changes per hour, extracted over the stove |
| Hospital ward | 6 changes per hour, or wide-open cross-ventilation |
| Isolation room for airborne disease | 12 or more changes per hour, and the room kept at lower pressure than the corridor |
| Operating theatre | 20–25 changes per hour, filtered, the room kept at higher pressure than the corridor |
| Workshop with fumes | 6–10 changes per hour plus extraction at the source |
| Mine working | about 3 m³ per minute for each person, and air moving at least 0.25 m/s past the face |
Fans and the fan laws
The centrifugal fan (a paddle wheel in a snail-shaped case, Centrifugal Pumps and Fans) makes high pressure and suits ducts, filters and dust. The axial fan (a propeller in a ring) moves large volumes against little resistance and suits a hole in a wall. Every fan obeys the fan laws: air flow rises in proportion to speed, pressure with the square of speed, and power with the cube. Double the speed and you get twice the air at four times the pressure — for eight times the power. Change pulleys a little at a time, or you burn out the motor.
What you need
| Item | For |
|---|---|
| Sheet iron 0.5–1 mm, galvanised if possible (Sheet Metal and Rolling) | ducts, hoods, cyclones, fan casings |
| Boards, clay, tarred canvas | mine ducts, windcatchers |
| A fan and its drive: The Electric Motor or line shaft (Belts, Chains and Power Transmission) | extraction, mines, coolers |
| Wood wool (fine softwood shavings) or straw | evaporative cooler pads |
| Felted wool or tight-woven cotton (Felt, Cotton) | bag filters |
| A water manometer: a glass U-tube half full of water (Pressure and Vacuum Gauges) | fan pressure, filter dirt |
| Wet-and-dry thermometers (Rain Gauges, Anemometers and Weather Stations) | judging evaporative cooling |
| A refrigerating plant, pump and finned coils (Ice and Refrigeration, Heat Exchangers) | air conditioning |
Natural ventilation
Vents, ridges and clerestories
Before any fan, put openings where the physics wants them:
- Low inlets, with shutters, on the side the summer wind comes from.
- High outlets as close to the ridge as you can: a ridge vent (a raised cap along the ridge, open at the sides), a louvred lantern, or high windows (clerestories) on the leeward side (Roofs).
- Make the outlet area at least equal to the inlet area. For a hot workshop, give 3–5% of the floor area to each.
- In cold weather, a trickle vent — a slot of 40–80 cm² per room, high up — gives the minimum air without a draught.
The Nightingale ward (Running a Hospital) is the model: about 9 m wide, tall windows facing each other on both sides, a 4–5 m ceiling.
The windcatcher
A windcatcher (Persian badgir) is a tower that catches the stronger, cleaner breeze above the rooftops and sends it down into the house. When the wind drops, the sun-warmed tower works as a stack and draws air out.
- Build a shaft of brick or timber and clay plaster, about 0.6 × 0.6 m inside per room it serves (1 × 1 m for a large hall), rising 2–4 m above the roof.
- Open the top towards the prevailing wind. Where the wind changes, divide the shaft with two crossed walls into four flues opening on different sides: the one facing the wind blows down, the others suck.
- Open the bottom into the room with a shutter for cold weather, and net the top against birds.
- To cool the air, hang porous clay jars of water or a wet charcoal or straw screen in the bottom of the shaft, as in the zeer pot (Ice and Refrigeration). In dry heat this cools the incoming air by 8–12 °C.
Ducted ventilation
The ventilation duct
A ventilation duct is a pipe for air, sized by the air speed you want: 3–5 m/s for wards and houses (quiet), 6–10 m/s for workshops and mines, 15–20 m/s for sawdust and grain dust and 20–23 m/s for grinding dust (slower, and the dust settles and chokes the duct). Area (m²) = air flow (m³/s) ÷ speed (m/s). For 0.5 m³/s at 5 m/s you need 0.1 m², which is a round duct of 36 cm or a square one of 32 × 32 cm.
How to make it:
- Round is best: stiffest, least metal, least friction. Roll sheet iron 0.5–0.8 mm thick (up to 1 mm for dust ducts) round a wooden former and close it with a folded lock seam (Sheet Metal and Rolling). Make lengths of 1–1.5 m.
- Joints. Crimp (corrugate) one end of each length a little smaller so it slides 5 cm into the next, with the crimped end pointing downstream so dust does not catch on the lip. Rivet it and seal with clay and linseed oil.
- Bends are made of 4–5 short angled pieces (gores). Make the radius of the bend's centre line at least 1½ times the duct's diameter; a sharp elbow wastes as much pressure as 10–20 m of straight duct.
- Branches join at 30–45°, never at right angles, and the main must grow larger after each branch so the speed stays even.
- Dampers — a round plate on a spindle across the duct, with a handle to lock it — balance the branches. Hang the duct from iron straps every 2–3 m.
- For mines and tunnels, use a trunk of planks 30–40 cm inside sealed with clay, or a tube of tarred canvas on hoops. Blowing to the face clears gas there but sends foul air back past the miners; sucking takes dust and smoke straight out. Keep the duct end within 10 m of the face and patch every leak (Mining and Tunnelling, Tunnels and Rock Drilling).
Friction. A 30 cm duct carrying air at 5 m/s loses about 1 Pa per metre. A long system of ducts, bends, hoods and a filter can need 500–1,500 Pa — far more than the stack effect can give, so a centrifugal fan is the usual choice.
The extractor fan
An extractor fan pulls air out of a room or a hood and throws it outside.
A simple wall fan (axial).
- Line a round hole in the wall with a short sheet-iron ring as deep as the blades are wide.
- Make a propeller 30–60 cm across of 4–6 blades of 1 mm sheet iron or thin hardwood riveted to a hub, each twisted to meet the air at 25–35° near the hub and 15–20° at the tip.
- Keep the gap between blade tips and ring to 2–5 mm; a big gap lets air swirl back round the tips.
- Drive a 40 cm fan at 900–1,500 turns a minute by belt or The Electric Motor (Fans, Vacuum Cleaners and Washing Machines). It moves roughly 0.5–1 m³/s against little resistance.
- Fit gravity shutters outside: light slats hinged at the top that the outflow pushes open and that fall closed when the fan stops.
For ducts, hoods and dust, use a centrifugal fan with radial (straight) blades (Centrifugal Pumps and Fans); they shed dust where curved ones clog. Put it after the dust collector so it handles clean air. A manometer tapped into the duct before it should show 300–1,000 Pa (3–10 cm of water) of suction.
Catching fumes and dust at the source
The best ventilation takes the dirt away before it reaches anyone's face. A hood — the smoke hood over a forge is the oldest kind — sits as close to the source as possible and sucks.
The air speed a hood makes falls off very fast with distance. For a plain open duct end, the flow needed is
air flow (m³/s) = capture speed (m/s) × (10 × distance² + face area of the hood)
with distance in metres from the hood to the source. A flange (a flat collar round the hood mouth) cuts this by a quarter.
The capture speed needed at the source is 0.25–0.5 m/s for fumes rising gently from a tank, 0.5–1 m/s for soldering, welding and a forge, 1–2.5 m/s for sawing and sanding, and 2.5–10 m/s for grinding wheels and sand blasting.
Example: a 15 cm flanged hood held 20 cm from a welding job: 0.75 × 0.75 × (10 × 0.04 + 0.018) ≈ 0.24 m³/s. Pull the same hood back to 40 cm and you need nearly four times as much. Move the hood, not the fan.
A grinding wheel gets a hood that wraps all but the working part of the wheel, with the duct leaving in the direction the sparks fly; it is also the wheel guard (Precision Grinding). A saw bench gets a box under the blade (Planers, Thicknessers and Woodworking Machines); an acid tank gets a slot hood along its back edge; a chemistry bench gets a fume cupboard, a glazed box with a sliding sash, sucked so that 0.5 m/s flows in through the open front.
The dust collector
Dust sucked from machines must not be blown into the street in a cloud. A dust collector catches it. The crudest is a settling chamber, a big box in which the air slows below 1 m/s so that chips and shavings fall out.
The cyclone is the most useful collector you can make from sheet iron. Dusty air enters a cylinder sideways at 15–20 m/s and spins down a cone; the dust is flung to the wall and slides into a bin; the cleaned air turns up through a central pipe. It catches everything bigger than about a hundredth of a millimetre — shavings, sawdust, grain dust, grit — with no moving parts. Proportions, for a body diameter D:
| Part | Size |
|---|---|
| Cylinder height | 2 D |
| Cone height | 2 D |
| Dust outlet at the bottom of the cone | D/4 |
| Inlet, rectangular, tangential | D/2 high × D/4 wide |
| Central outlet pipe | D/2 across, reaching down 5D/8 inside |
For 0.5 m³/s at 18 m/s the inlet must be 0.028 m²; its area is D²/8, so D = 47 cm. Expect a pressure loss of 500–1,500 Pa. The dust bin must be airtight, or air leaks up the cone and lifts the dust back out.
The bag filter stops fine dust — flour, sanding dust, cement. Hang tubes of felted wool or tight-woven cotton, 15–20 cm across and 2–3 m long, closed at the top, their open mouths fixed in a plate over a hopper. Allow about 1 m² of cloth per cubic metre of air per minute. The dust cake on the cloth filters best but chokes the flow: with the fan stopped, shake the bags with a lever on the frame when a manometer across them reads about 1,000 Pa.
Danger Dust explosions. Flour, sugar, sawdust, coal and aluminium dust hanging in air burn in a flash; a spark from a nail sucked into a fan, a hot bearing or a naked light has blown apart mills and mines. Keep a magnet or stone trap before the fan; put dust collectors outdoors, with a light blow-out panel held by weak catches; never let dust lie thick on beams; no flames.
Cooling with water: the evaporative cooler
Each litre of water evaporated takes away about 2.4 MJ of heat. An evaporative cooler (desert cooler, swamp cooler) blows outside air through wet pads into the house — the zeer pot of Ice and Refrigeration with a fan. In a hot, dry climate it is nearly as good as air conditioning for a tenth of the power.
Will it work here? It can only cool down to the wet-bulb temperature — the reading of a thermometer whose bulb is wrapped in wet cloth and swung in the air (Rain Gauges, Anemometers and Weather Stations). A good cooler gets 70–85% of the way there:
air leaving the cooler ≈ dry temperature − 0.8 × (dry temperature − wet-bulb temperature)
At 38 °C dry and 21 °C wet bulb (a desert afternoon), it delivers air at about 24 °C. At 32 °C dry and 27 °C wet bulb (a humid coast), it gives 28 °C and makes the air muggy — not worth it.
Building one:
- Box. A wooden or sheet-iron box about 70 cm cube for a room of 30–40 m², set in a window or wall opening.
- Pads on three sides: 5–10 cm mats of wood wool (fine shavings of straight softwood; aspen and poplar are classic) or straw between two wire meshes. Air should pass them at no more than about 1 m/s — about 0.3 m² of pad per 1,000 m³/h.
- Water. A tray 5–10 cm deep in the bottom, and a small pump or header tank dripping water along a perforated pipe over the top of each pad, so the pads are wet all over but not streaming. Top up about 5–7 litres per hour per 1,000 m³/h of air on a hot day.
- Fan. A squirrel-cage or axial fan blowing through the box, sized for 20–40 air changes an hour — far more than refrigerated cooling, because the air is only a little cooler.
- Exhaust. Open windows on the far side; the air must flow through and out, or the room just becomes damp.
- Clean the tray weekly and replace pads each season; stagnant water breeds bacteria and mosquitoes.
Air conditioning
Air conditioning controls temperature, humidity (water vapour in the air), cleanliness and movement together. In a humid climate the air must be dried as well as cooled, or people stay clammy and mould grows.
Air at 30 °C can hold about 27 g of water vapour per kilogram; at 10 °C it can hold only 7.6 g. Pass humid air over a metal coil colder than its dew point (the temperature at which dew forms on a cold glass), and water condenses on the coil and drips off — the air leaves both cooler and drier. A coil at 6–8 °C fed with chilled water does this well. The air may then be too cold, so a small reheat coil warms it back to 16–18 °C before it enters the room.
The plant
The honest, safe way to air-condition with the means of this book is the chilled-water system already outlined in Fans, Vacuum Cleaners and Washing Machines:
- Chiller. One ammonia refrigerating machine (Ice and Refrigeration) in a well-ventilated outbuilding chills water to about 6–7 °C through a heat exchanger. The ammonia never enters the occupied building.
- Pipes. Insulated pipes (Insulation and Keeping Buildings Warm or Cool) and a centrifugal pump carry the cold water to the building; it returns at about 12 °C.
- Air handling unit. The air handling unit (AHU) is a sheet-iron box through which all the air passes, in order:
- a mixing box with dampers for fresh and returning air: 10–30% fresh air for ordinary rooms, 100% for operating theatres and isolation wards;
- filters (below);
- the cooling coil: finned copper tubes carrying chilled water (Heat Exchangers), with air crossing its face at no more than 2.5 m/s, or drops are blown off into the duct;
- a drip tray sloping to a drain with a water trap (a U-bend kept full of water), or the fan sucks air up the drain;
- a heating coil from the boiler (Hot Water and Central Heating) for reheat and winter;
- the fan, a belt-driven centrifugal.
- Supply ducts to ceiling diffusers (grilles that spread the air), and return grilles low on the far side of each room.
How much? A room in a hot climate gains about 80–150 W per m² of floor from sun, walls and lamps, and 100 W per person. Each m³/s of air carries away 1.2 kW for each 1 °C it is supplied below room temperature, so:
air flow (m³/s) ≈ heat gain (kW) ÷ (1.2 × temperature difference)
A 40 m² ward gaining 5 kW, supplied 10 °C below the room, needs about 0.42 m³/s (1,500 m³/h). The refrigerating plant must also remove the heat and moisture of the fresh air — allow roughly 50% more.
Filters
An air filter catches dust and germs before they reach the rooms or the coil. Use them in stages: a coarse pre-filter of oiled wire mesh or loose wool between meshes (washable) for insects and lint; a medium filter of pleated cotton or felt for visible dust and pollen; a fine filter of glass-fibre pads (Glass Fibre and Glass Wool) for smoke and germ-carrying droplets; and for operating theatres a HEPA filter (high-efficiency particulate air), deep-pleated paper of very fine glass fibre that stops 99.97% of particles 0.3 µm across.
Pleat the filter material so a large area of cloth fits in a small frame and the air passes through the cloth itself slowly, at a few centimetres a second. Seal the frames into the box with felt gaskets: air that goes round a filter is not filtered. Put a water manometer across the filter bank. A clean filter loses 50–150 Pa; change or wash it when the loss doubles.
Pressure and direction in hospitals
Operating theatres get more air supplied than extracted, so air leaks out through door gaps and corridor dust stays out; supply over the table, extract low at the corners. Isolation rooms for tuberculosis, measles and other airborne diseases (Infectious Diseases) get 10–15% more extracted than supplied, so air leaks in; blow their exhaust out high above the roof, far from windows and inlets. Check daily with a strip of tissue held at the gap under the closed door: it must lean into the isolation room and out of the theatre.
How to tell it worked
- Smoke test. Light a smouldering rag or incense: in a well-ventilated room the smoke drifts steadily to the outlet and is nearly gone in 20 minutes (about 6–10 changes an hour). Puffed at the working position, it should be pulled straight into the hood.
- The cyclone sends almost nothing out of the top: hold a dark cloth in the outlet air for a minute and look.
- The evaporative cooler delivers air within a few degrees of the wet-bulb reading.
- The air conditioning holds a room near 24 °C, and the drip tray drain runs steadily on humid days.
Note Troubleshooting. Stack ventilation runs backwards → the room is colder than outside (common in summer). Rely on wind and night ventilation. Duct choked with sawdust → air too slow. Shrink the duct or close unused branches so the speed stays at 18–20 m/s. Fan roars but little air moves → filter or cyclone bin choked, a damper shut, or the fan running backwards (a centrifugal fan running backwards still blows the right way, but moves much less air — swap two wires of a three-phase motor or cross the belt). Cyclone blows dust out the top → air leaking in at the bin, or inlet too slow. Seal the bin; reduce the inlet size. Water spitting from the cooling coil into the duct → face speed above 2.5 m/s or a blocked drain trap. Musty smell from the plant → wet, dirty filters or a drip tray holding standing water. Clean, slope the tray, disinfect with chlorine (Chlorine and Bleach).
Dangers
Danger Carbon monoxide and fire draughts. A strong extractor fan in a tight house can pull air down the chimney of a stove or water heater and fill the room with carbon monoxide. Whenever a fan extracts from a room with a fire, give the room a fresh-air inlet at least as large as the fan's duct, and test with smoke at the fireplace while the fan runs.
Danger Ammonia. Keep the ammonia refrigerating machine outside the occupied building, in a well-ventilated room with doors opening outwards and an emergency exhaust fan whose switch is outside the door. A large ammonia leak can kill in minutes (Ammonia, Ice and Refrigeration).
- Fans cut fingers. Guard every fan inlet and outlet with mesh no coarser than 12 mm, and every belt with a cover.
- Legionnaires' disease and mould. Wet coolers, drip trays and cooling towers (Cooling Towers and Spray Ponds) breed bacteria in warm standing water. Drain, clean and chlorinate regularly; place cooling towers away from air intakes.
- Spreading infection. Never recirculate air from an isolation ward to other rooms; never let an isolation room's exhaust discharge near a window or air inlet.
What this unlocks
Controlled air makes possible the operating theatre (Basic Surgery) and safe isolation (Running a Hospital), deep mines and long tunnels, Clean Rooms for Making Microchips, textile mills held at a fixed humidity (Textile Machinery), and productive work in the hottest parts of the world. The same coils and fans, with the refrigerating cycle run in reverse, give Heat Pumps and District Heating.
How it was first done
Windcatchers have cooled houses in Egypt, Persia and the Gulf for a very long time; Egyptian tomb paintings more than three thousand years old probably show wind scoops on house roofs. Agricola's De re metallica (1556) shows bellows and horse-driven fans ventilating German mines; steam-driven fans such as the Belgian Guibal fan of the 1860s replaced mine furnaces.
Florence Nightingale's Notes on Hospitals (1859) made fresh air the first rule of ward design. In 1902 the American engineer Willis Carrier designed a plant for a printing works in Brooklyn, New York, that cooled and, above all, dried the air so that paper did not swell and spoil the colour printing; his 1906 patent and his 1911 chart of air and moisture made air conditioning a science. The HEPA filter was developed in the 1940s to catch radioactive dust in the American atomic bomb project, and is now the standard filter of operating theatres and Clean Rooms.