Electricity Meters and Billing

How to measure the electricity each house and workshop uses, so a grid can charge fairly and pay for itself — the electrolytic meter, the motor meter, the induction kilowatt-hour meter with its spinning disc, and the coin prepayment meter — how to build, read, test and seal them, and how to set tariffs.

Difficulty
●●●●●
Time
An afternoon to make an electrolytic meter; a few weeks to build and calibrate a first induction meter; minutes to read and test one in service
Steps from zero
27 prerequisites →

You need first

Measuring ElectricityPower Lines and Distribution

This unlocks

—
The full path from nothing — 27 steps before this one
  1. Fire
  2. Cordage and Rope
  3. Stone Tools
  4. Finding and Preparing Clay
  5. Finding and Identifying Ores
  6. Hunting and Trapping
  7. Basic Woodworking
  8. Charcoal
  9. Pottery
  10. Hides and Leather
  11. Fermentation
  12. The Wheel and Axle
  13. Bellows
  14. Gears
  15. Copper Smelting
  16. Iron (the Bloomery)
  17. The Waterwheel
  18. Blacksmithing
  19. The Battery
  20. Magnets
  21. Copper Wire
  22. The Electromagnet
  23. The Generator
  24. Measuring Electricity
  25. The Transformer
  26. Wiring and Electrical Safety
  27. Power Lines and Distribution
  28. Electricity Meters and Billing

Do them roughly in this order. See it on the tech tree →

Why it matters

A grid costs money every day: fuel or water for the The Generator, wire, poles and transformers (Power Lines and Distribution), and people to run and mend it. Someone must pay. Without meters you charge a flat fee per lamp or per house, and every user leaves lights burning all night because it costs them nothing more. The plant overloads, voltage sags at the end of the line, and careful users pay for careless ones.

A meter counts the energy each customer uses. Bills become fair, people switch things off, and the grid's managers learn how much power is used where and when, which tells them where to build next. A good meter runs for twenty years or more without attention, is accurate to about 2%, and cannot easily be cheated.

How it works

Energy is power times time

Power is how fast energy is used, in watts: volts × amps, for a heater or lamp (Measuring Electricity). Energy is power multiplied by how long it is used. The billing unit is the kilowatt-hour (kWh), often just called a unit: 1,000 watts for one hour, or a 100 W lamp for ten hours, or 3.6 million joules.

A meter must multiply volts by amps at every moment and add up the result over a month. There are three ways to do this:

  1. Chemistry: let a fixed fraction of the current carry metal from one plate to another. The metal moved is proportional to amps × hours. On a supply of steady voltage, that is proportional to energy.
  2. A motor whose speed is proportional to power, turning a counter. This is the motor meter and the induction meter.
  3. Electronics that sample voltage and current thousands of times a second and add up their product.

The braked motor

The second method is the clever one. Make a small motor whose driving force (torque) is proportional to the power going through it. Brake it with a copper or aluminium disc turning between the poles of a permanent magnet. The magnet induces eddy currents in the moving disc, which drag it back with a force proportional to its speed (Magnets). The motor speeds up until drag equals drive, so its speed is proportional to the power. Count the turns and you have counted energy. Double the load and the disc turns twice as fast.

What you need

Item Notes See
Copper sulfate or zinc sulfate, copper or zinc plates, glass jars Electrolytic meter Electrolysis
Constantan or manganin wire Shunts and resistors that do not change with heat Measuring Electricity
Fine enamelled copper wire, 0.1 mm Voltage coils Copper Wire
Thin silicon-steel or soft-iron sheet Laminated magnet cores The Transformer
Pure aluminium sheet 0.8–1 mm Disc Aluminium
Hard permanent magnet steel Brake magnet Magnets
Brass, small gears, a sapphire or hard steel pivot Spindle, register Gears, Clockwork, Music Boxes and Counting Machines, Synthetic Gems
Accurate ammeter, voltmeter, a clock with a seconds hand Testing Measuring Electricity, The Mechanical Clock
Lead, wire, sealing pliers Seals Lead

Method 1: The electrolytic meter

This is the first meter to build. It needs no moving parts and works only on direct current (DC).

Electrolytic meter (DC) Coin prepayment meter from supply to house Shunt, 0.01 Ω Fixed resistor about 1.7 Ω about 1/200 of the current takes this path Cu Copper sulfate in a glass jar This plate gains copper weigh it every month: 1.186 g per amp-hour Coin slot, knob coin falls Locked cash box + credit per coin Differential gear − credit as units are used Meter disc Credit wheel notch = zero Switch to the house at zero, the lever drops into the notch and opens the switch
Fig. 1 Two simple meters. Left: the electrolytic meter. A low-resistance shunt carries almost all the house current; a fixed small fraction flows through a jar of copper sulfate and carries copper from one plate to the other. Weighing the plates each month shows the amp-hours used. Right: the coin prepayment meter. Each coin turns the credit wheel forward; the meter disc turns it back; when credit reaches zero the switch opens.
  1. The cell. A small glass jar of copper sulfate solution (about 150 g per litre, with a few drops of sulfuric acid) holds two clean copper plates, 5 × 3 cm, 1 cm apart. Use zinc plates in zinc sulfate if you prefer, as Edison did.
  2. The shunt. A strip of constantan or manganin, about 0.01 Ω, carries the house current. Across it connect the cell in series with a fixed resistor of about 1.7 Ω of the same alloy. The cell itself adds about 0.3 Ω, so about 1/200 of the current goes through the cell. The fixed resistor is large compared to the cell, so changes in the cell's resistance with temperature matter little.
  3. Before fitting, dry and weigh the negative plate on a chemical balance to 10 mg (Balances, Steelyards and Weighing Machines).
  4. Each month, take the plate out, rinse it in clean water, dry it, weigh it again, and replace it with a fresh one.

Working it out. One ampere for one hour deposits 1.186 g of copper (1.22 g of zinc). A house on a 110 V DC supply using 1 kWh a day draws about 9.1 amp-hours a day. One two-hundredth of that, 0.045 Ah, lays down about 54 mg of copper a day, or 1.6 g a month. Divide the gain in weight by the meter's constant to get kWh.

Calibrate each meter, not just the design: pass a known current (5 A, measured on a good ammeter) for a known time (2 hours) through the shunt, weigh the copper gained, and work out the grams per kWh at your supply voltage. Mark it on the meter.

Limits. It shows amp-hours, not true energy: if the voltage falls, the customer is charged for energy they did not get. It needs a weighing every month, so it suits a small grid. Keep it from freezing (Edison put a small lamp in the meter box, switched on by a thermostat, Thermostats and Automatic Control). It does not work on AC.

Method 2: The motor meter

Elihu Thomson's recording wattmeter (1889) is a small motor with no iron, so its torque is exactly proportional to volts × amps, on DC or AC:

  • Two fixed field coils of a few turns of heavy wire carry the load current.
  • A light armature of fine wire, wound on a former of wood or card, turns between them. It is fed through a small silver commutator and a resistor of several thousand ohms from the supply voltage.
  • On the same spindle, a copper disc turns between the poles of two permanent magnets (the brake), and a worm at the top drives a dial register.
  • A small extra coil across the supply gives just enough torque to overcome friction at light loads.

It reads true watt-hours and served DC grids for decades, but its brushes and commutator need cleaning. On AC, the induction meter is simpler and better.

Method 3: The induction kilowatt-hour meter

The induction meter has only one moving part, an aluminium disc on a spindle, with no brushes and no wires to it. It is the meter in the glass-fronted box by the door of nearly every AC-wired house of the 20th century.

NS Register counts disc turns as kWh Voltage magnet ~10,000 turns of fine wire, across the supply lag coil: power-factor adjustment light-load vane: overcomes friction Aluminium disc Current magnet a few turns of thick wire, carries the load Worm . on spindle Black mark Brake magnet permanent slide outward to slow the meter, inward to speed it up Jewel pivot sapphire or hard steel
Fig. 2 The induction kilowatt-hour meter. The voltage magnet above the disc and the current magnet below it make magnetic fields that sweep across the aluminium disc and push it round. The permanent brake magnet holds its speed proportional to the power. The worm on the spindle turns the register. Adjusting screws set the speed at full load, light load and lagging loads.

How it turns

The voltage magnet above the disc carries thousands of turns of fine wire across the supply. Because the coil is highly inductive, its magnetism lags the voltage by almost a quarter of a cycle. The current magnet below carries the load current, and its magnetism rises and falls with the current. The two fields peak at different moments and at different places across the disc, so together they make a field that sweeps across it. Eddy currents in the aluminium are dragged along by the sweeping field, like the rotor of an induction motor (The Electric Motor). The torque is proportional to volts × amps × power factor: the true power, exactly what you want to charge for.

Build it

  1. Disc: pure aluminium, 0.8–1 mm thick, 80–100 mm across, turned flat and true. Paint a black mark on its edge so you can count turns.
  2. Spindle: steel or brass, vertical, with a worm cut near the top. The bottom rests on a hardened steel or sapphire pivot in a jewel cup (Synthetic Gems, Watches and Small Clocks); the top runs in a small loose bush. Friction must be tiny: a breath on the disc should set it turning.
  3. Voltage magnet: an E-shaped stack of thin laminations of silicon steel or soft iron (The Transformer), its centre leg ending close above the disc. For 230 V wind about 10,000 turns of 0.1 mm enamelled wire (for 110 V, about half); it should draw only 1–2 W.
  4. Current magnet: a U-shaped laminated core whose two poles come up under the disc, either side of the voltage pole. Wind it with a few to a few dozen turns of wire thick enough for the full rated current, for example 10 A.
  5. Brake magnet: a C-shaped permanent magnet of hard magnet steel, poles 2–3 mm apart with the disc edge between them. Age it by heating to boiling water temperature and knocking it several times, so its strength does not drift over the years (Magnets, Permanent Magnets).
  6. Register: the worm drives a train of gears to either a row of dials or a cyclometer (number wheels like a car's odometer, Clockwork, Music Boxes and Counting Machines). Choose the gearing to suit the meter constant, the number of disc turns per kWh: with 600 turns per kWh, the units dial must turn once every 6,000 disc turns.
  7. Case: a base of cast iron or moulded insulation, a cover with a glass window, and a terminal block with separate sealed cover. Mount it vertical within a degree or two: a tilted meter has more friction.

The adjustments

  • Full-load speed: slide the brake magnet. Moving it outward towards the rim brakes harder and slows the meter; inward speeds it up.
  • Light-load: a small adjustable copper vane under the voltage pole gives a tiny extra forward push that just overcomes friction, so the meter is accurate at 5–10% load.
  • Power factor (lag): a lag coil, a closed loop of wire round the voltage pole with a resistance you can vary, sets the voltage field to lag by exactly a quarter cycle, so the meter reads correctly with motors and other loads that draw current out of step (Synchronous Motors and Converters).
  • Anti-creep: two small holes drilled in the disc on opposite sides, or a tiny iron tag on the spindle that the voltage magnet attracts, stop the light-load push from turning the disc slowly when nothing is switched on.

Bigger loads

For a three-phase workshop, stack two or three driving elements on one spindle, each measuring one phase. For currents above about 100 A, feed the current magnet from a current transformer (a ring core with the heavy cable as its one-turn primary and a secondary giving 5 A at full load) and multiply the register reading by the ratio.

The prepayment meter

A prepayment meter sells electricity in advance, so poor or unreliable payers can still be supplied and no bills go unpaid.

The coin meter adds a mechanism to an ordinary induction meter:

  1. A slot takes one size of coin. Turning the knob with a coin in it rotates a credit wheel forward by a fixed angle; the coin drops into a locked cash box.
  2. The meter's disc, through its register train, turns the same credit wheel backwards through a differential gear as energy is used.
  3. The credit wheel works a switch. While credit is above zero the switch is closed; when it reaches zero it opens and the lights go out.
  4. Change wheels in the gearing set how many kWh one coin buys, so the price can be changed by the supplier without a new meter.
  5. A stop limits the credit that can be bought at once, so the cash box does not overflow. A coin counter lets the collector check that coins taken match coins credited.

Token and keypad meters later replaced coins with cards or with a long number bought at a shop, which an electronic meter checks and adds as credit.

The load limiter is the cheapest scheme of all, used for small rural customers: no meter, a flat monthly fee, and a current-limiting cut-out (a small thermal or magnetic trip, Motor Starters, Contactors and Protection) that switches off if the house draws more than, say, 0.5–1 A. It allows a few lamps and a radio but no heater, and costs a tenth of a meter.

Warning Prepayment meters cut off the poorest households first, often in winter and at night. Fit an emergency credit button that allows a day or two more, do not disconnect the sick or those with small children on medical equipment, and do not charge prepayment customers a higher price than others.

Reading a meter

A cyclometer shows the reading directly as a row of numbers.

Dial registers have four to six small dials, each worth ten times the one to its right. Neighbouring dials turn in opposite directions; follow the numbers round each dial.

  1. Read from left to right.
  2. For each dial, write the number the pointer has just passed: the lower of the two numbers it lies between. Between 9 and 0, it is 9.
  3. If a pointer seems to sit exactly on a number, look at the dial to its right. If that dial shows 9 (it has not yet passed 0), the left dial has not quite reached its number: take one less.
  4. Subtract last month's reading from this month's. That is the kWh used.
0 1 2 3 4 5 6 7 8 9 ×10,000 0 1 2 3 4 5 6 7 8 9 ×1,000 0 1 2 3 4 5 6 7 8 9 ×100 0 1 2 3 4 5 6 7 8 9 ×10 0 1 2 3 4 5 6 7 8 9 ×1 1 4 7 9 6 Reading: 14,796 kWh The middle pointer looks as if it is on 8, but the next dial shows 9 (not yet past 0), so take 7. meter cover and terminal cover K7 Seal wire through holes drilled in the cover screws Lead seal squeezed with pliers that stamp the inspector's mark; broken = investigate
Fig. 3 Reading a five-dial register. Neighbouring dials turn in opposite directions. Take the number each pointer has just passed. The middle pointer looks as if it is on 8, but the dial to its right shows 9, so it has not yet reached 8: the reading is 14,796. Below: a lead seal on a wire through the cover screw and the terminal cover, squeezed with pliers that stamp the inspector's mark.

Record readings in a route book or on cards (Punched-Card Tabulating Machines), with the date. A reading far from the usual should be checked before the bill goes out: misreading one dial changes a bill tenfold.

Testing and sealing

Testing a meter

The disc test, with no instruments but a known load and a watch:

power (kW) = 3,600 × turns ÷ (meter constant × seconds)

A 1,000 W heater on a meter of 600 turns per kWh should give 10 turns in 60 seconds. If it takes 61.2 seconds, the meter is running 2% slow.

On the test bench, compare the meter with an accurate wattmeter or a precise ammeter and voltmeter on a pure resistance load (Measuring Electricity):

Test Load Accept
Full load 100% of rated current, unity power factor Within ±2%
Light load 10% of rated current Within ±2.5%
Lagging 100% current through a choke, power factor 0.5 Within ±2.5%
Starting About 0.5–1% of rated current (one 25 W lamp on a 10 A, 230 V meter) Disc starts and keeps turning
Creep No load, voltage 10% above normal Disc does not make one full turn in 15 minutes

Phantom loading. To test many meters at once without burning kilowatts, put their current coils in series on a low-voltage, high-current transformer (a few volts), and feed their voltage coils from the normal supply. Only a few watts are wasted for meters reading many kilowatts. Test every new meter, every repaired one, and a sample of those in service every few years.

Sealing

Each meter cover has its screws drilled across. Thread a twisted steel or copper seal wire through the screw heads and the case, and squeeze a soft lead seal onto the ends with sealing pliers whose jaws are engraved with the inspector's mark and number (Lead). The terminal cover and the supplier's service fuse (cut-out) are sealed the same way. Nobody can open the meter or connect before it without breaking a seal.

Signs of tampering: broken or re-squeezed seals, holes in the cover or glass, scratch marks on the disc, the disc not turning with lamps lit, a magnet stuck to the case, scorched wires, or the disc turning backwards (input and output swapped). Fit a ratchet so the register cannot run backwards.

Tariffs

A tariff is the rule that turns kWh into a bill. It must cover the cost of the grid, be fair, and be simple enough to explain.

  • Flat rate per lamp or per house: no meter, cheap to run, encourages waste.
  • Simple rate: a price per kWh. Fair, but a house that uses almost nothing pays almost nothing towards its poles, wires and meter reading.
  • Two-part tariff: a fixed standing charge per month for the connection, plus a price per kWh. Example: standing charge 2.00, plus 0.15 per kWh; a house using 90 kWh pays 2.00 + 13.50 = 15.50.
  • Block tariff: the first 30 kWh a month at a low lifeline price, so every household can afford light and a radio, and the rest at a higher price.
  • Time-of-day: a meter with two registers switched by a time clock (Synchronous Motors and Converters). Cheap night units fill the generator's idle hours for water heating, pumping and battery charging.
  • Maximum demand: big users also pay for their highest load, because that sets the size of the plant needed. A maximum demand indicator is a loose pointer on the meter that is pushed forward by the register over each half hour and then left behind when the pusher resets: it shows the largest half-hour's use since the inspector last reset and sealed it. Factories with many motors may also be charged for poor power factor.

Bill monthly or quarterly, read on a fixed route, and give every customer the two readings, the units, the price and the total, so they can check it.

How to tell it worked

  • Total of all customers' meters over a month is 90–95% of what the plant's own meter sent out. The difference is line loss and theft (Power Lines and Distribution). A much larger gap means faulty meters or stolen power.
  • A disc test on any meter falls within ±2% of the true load.
  • No meter turns with all loads off.
  • Customers' bills follow the seasons smoothly; a sudden halving or doubling is investigated.

Note Troubleshooting. Disc creeps with nothing on — light-load vane set too far forward, or anti-creep tag missing; check also for a small leakage current from damp wiring. Meter slow at light load, right at full load — friction: dirty or worn pivot jewel, disc rubbing a magnet, or meter not vertical. Meter wrong only with motors running — lag adjustment off; test at 0.5 power factor. Meter drifting slow over years — brake magnet strengthening is rare; more often the pivot is wearing. Clean and re-jewel. Electrolytic meter reads low in winter — a cold cell has more resistance, so less of the current passes through it; keep the meter box warm, and recalibrate in the cold season.

Dangers

Danger A meter sits on the live supply side of the customer's fuses: only the supplier's service fuse protects it, and a fault there can draw hundreds of amps. Never open a meter or its terminal cover while connected. Pull the service fuse, check the terminals are dead with a tester, and work with one hand where you can (Wiring and Electrical Safety).

  • Current transformers must never be left with their secondary open while the main cable carries current: the open secondary rises to a lethal voltage and the core overheats. Short the secondary before disconnecting the meter.
  • Phantom-load test benches have both a mains-voltage circuit and a high-current circuit; guard the terminals.
  • Copper and zinc sulfate are poisonous if swallowed; label the jars and keep them from children.
  • Theft by bypassing a meter is dangerous to the thief and to line workers, who may find a line live that should be dead. Investigate rather than ignore it.

What this unlocks

Fair billing lets a grid pay for itself and grow (Power Lines and Distribution). Meter readings, kept on cards (Punched-Card Tabulating Machines) or later in a The Computer, show where load is growing and where new lines and transformers are needed. The same turning-and-register idea measures water and gas (Water and Gas Meters), and electronic meters with remote reading (Telemetry and Remote Control) lead to the "smart" grids that match demand to solar and wind power.

How it was first done

Thomas Edison billed the first customers of his Pearl Street station in New York (1882) with zinc electrolytic meters, weighed monthly. Elsewhere in the 1880s, inventors including Hermon Aron in Germany built clock meters, in which the current altered the rate of a pendulum clock. Elihu Thomson introduced his recording wattmeter in 1889. In 1888 Oliver Shallenberger at Westinghouse made an induction meter for AC, using the rotating-field idea published that year by Galileo Ferraris; in 1889 Ottó Bláthy at Ganz in Budapest patented a true induction watt-hour meter, and the type, steadily refined, served for over a century. John Hopkinson proposed the two-part tariff in 1892. Coin prepayment meters spread in Britain from the 1890s. Electronic meters began to replace spinning discs in the 1990s.